§ 15.04.3.2015 — CBC Section 713.13.3 amended
Oakland Municipal Code (Supp. No. 103: codified through Ordinance No. 13873, adopted February 17, 2026) · Oakland Municipal Code § 15.04.3.2015
Corpus is an independent public-information project, not the official City of Oakland website. Stable reference: corpuslaw.us/code/42c088e5-6646-4e63-b353-664980599d06
15.04.3.2015 - CBC Section 713.13.3 amended.
In Section 713.13.3 add the following language: "Chute Access rooms are required to have mechanical ventilation at the minimum rate as specified in the California Energy Code, California Mechanical Code Table 403.7, or ASHRAE standard. The required mechanical ventilation shall incorporate a ducted exhaust and supply air system. Rated corridors shall not be used to convey ventilation air to or from the rooms and the mechanical ventilation system ductwork shall not be installed in the trash/linen chute shaft unless specifically approved by the building official. Mechanical ventilation required for the chute access rooms may be installed in a separate shaft adjacent to the trash/linen chute shaft with appropriate fire protection or shall originate and terminate to the exterior in an approved manner. The mechanical ventilation system or systems shall not compromise the integrity of the fire rating or structural components of the building and installation shall be in compliance with all applicable sections of the California Building, Fire, Energy, Green and Mechanical Codes."
(Ord. No. 13861, § 4, 9-15-2025)