§ 4-4.59 — Amendment: Required water supply
City of Ontario, California, Municipal Code (2026 S-32: Current through Ordinance 3338, passed 7-21-2026) · Ontario Municipal Code § 4-4.59
Corpus is an independent public-information project, not the official City of Ontario website. Stable reference: corpuslaw.us/code/a0bfd391-c6ee-45b7-b43a-a6ce940b4e31
Sec. 4-4.59. Amendment: Required water supply.
Section 507.5.1 of the CFC is amended to read as follows: 507.5.1 Where required. Where a portion of the facility or building hereafter constructed or moved into or within the City is more than 350 feet from a hydrant on a fire apparatus access road, as measured by an approved route around the exterior of the facility or building, on-site fire hydrants and mains shall be provided where required by the fire code official. Public or private fire hydrants shall be spaced a maximum of 350 feet apart." Exception: For Group R-3 and Group U occupancies, equipped throughout with an approved automatic sprinkler system installed in accordance with Section 903, the distance requirement of a private or public fire hydrant shall be spaced no more than 500 feet apart. (§ 2, Ord. 3320, eff. February 19, 2026)
Ask a question about Ontario law
Corpus searches the Ontario sections it holds and shows the ones that match, with their citations. Free, no sign-in.
