For AI agents: read the machine-readable documentation index at /llms.txt or the single-file full reference at /llms-full.txt.

§ 4-4.59 — Amendment: Required water supply

City of Ontario, California, Municipal Code (2026 S-32: Current through Ordinance 3338, passed 7-21-2026) · Ontario Municipal Code § 4-4.59

Corpus is an independent public-information project, not the official City of Ontario website. Stable reference: corpuslaw.us/code/a0bfd391-c6ee-45b7-b43a-a6ce940b4e31

Sec. 4-4.59. Amendment: Required water supply.

Section 507.5.1 of the CFC is amended to read as follows: 507.5.1 Where required. Where a portion of the facility or building hereafter constructed or moved into or within the City is more than 350 feet from a hydrant on a fire apparatus access road, as measured by an approved route around the exterior of the facility or building, on-site fire hydrants and mains shall be provided where required by the fire code official. Public or private fire hydrants shall be spaced a maximum of 350 feet apart." Exception: For Group R-3 and Group U occupancies, equipped throughout with an approved automatic sprinkler system installed in accordance with Section 903, the distance requirement of a private or public fire hydrant shall be spaced no more than 500 feet apart. (§ 2, Ord. 3320, eff. February 19, 2026)