§ 4-4.70 — Amendment: Appendix B Table B105.2 - Required Fire Flow for Buildings other than one- and two-family dwellings, Group R-3 and R-4 buildings and townhomes

City of Ontario, California, Municipal Code (2026 S-32: Current through Ordinance 3338, passed 7-21-2026) · Ontario Municipal Code § 4-4.70

Corpus is an independent public-information project, not the official City of Ontario website. Stable reference: corpuslaw.us/code/abf4dd80-12b0-42be-99c0-1747351e7ad2

Sec. 4-4.70. Amendment: Appendix B Table B105.2 - Required Fire Flow for Buildings other than one- and two-family dwellings, Group R-3 and R-4 buildings and townhomes.

Appendix B Table B105.2 is amended to read as follows: TABLE B 105.2 - REQUIRED FIRE FLOW FOR BUILDINGS OTHER THAN ONE- AND TWO- FAMILY DWELLINGS, GROUP R-3 AND R-4 BUILDINGS AND TOWNHOUSES AUTOMATIC SPRINKLER SYSTEM (Design Standard) | MINIMUM FIRE FLOW (gallons per minute) | FLOW DURATION (hours) No automatic sprinkler system | Value in Table B105.1(2) | Duration in Table B105.1(2) Section 903.3.1.1 of the California Fire Code | 50% of the value in Table B105.1(2)a | Duration in Table 105.1(2) at the reduced flow rate Section 903.3.1.2 of the California Fire Code | 50% of the value in Table B105.1(2)b | Duration in Table B105.1(2) at the reduced flow rate For SI: 1 gallon per minute = 3.785 L/m. a. The reduced fire flow shall be not less than 1,500 gallons per minute. b. The reduced fire flow shall be not less than 1,500 gallons per minute. (§ 2, Ord. 3320, eff. February 19, 2026)

Ask a question about Ontario law

Corpus searches the Ontario sections it holds and shows the ones that match, with their citations. Free, no sign-in.