§ 15.56.050 — Quality control

Municipal Code of the City of Rialto, California (Codified through Ordinance No. 1713, passed April 28, 2026. (Supp. No. 39)) · Rialto Municipal Code § 15.56.050

Corpus is an independent public-information project, not the official City of Rialto website. Stable reference: corpuslaw.us/code/aa1f021d-f382-43d9-9644-a4f488f949e5

15.56.050 - Quality control.

A. Pointing. All preparation and mortar pointing shall be performed with special inspection. Exception: At the discretion of the chief building official or his/her designee, incidental pointing may be performed without special inspection. B. Masonry Shear Tests. In-place masonry shear tests shall comply with U.B.C. Standard No. 2115. C. Existing Wall Anchors. Existing wall anchors utilized as all or part of the required tension anchors shall be tested in pullout according to U.B.C. Standard No. 21-8. The minimum number of anchors tested shall be four per floor, with two tests at walls with joists framing into the wall, and two tests at walls with joists parallel to the wall, but not less than ten percent of the total number of existing tension anchors at each level. D. New Bolts. One-fourth of all new shear bolts and combined tension and shear bolts in unreinforced masonry walls shall be tested according to the U.B.C. Standard No. 21-8. Exception: Special inspection in accordance with Building Code may be provided during installation in lieu of testing.

(Ord. 1250 § 1 (part), 1996)