§ 14.14.100 — Grease interceptor requirements
Municipal Code, City of Roseville, California · Roseville Municipal Code § 14.14.100
Corpus is an independent public-information project, not the official City of Roseville website. Stable reference: corpuslaw.us/code/f1f3c53d-619f-4ba3-9ecb-4a0e58019691
§ 14.14.100: Grease interceptor requirements.
A. Any FSE required by this chapter to provide FOG pretreatment shall install, operate and maintain an approved type and adequately sized grease interceptor necessary to maintain compliance with the objectives of this chapter. B. Grease interceptor sizing and installation shall conform to the then current edition of the Uniform Plumbing Code. Grease interceptors shall be constructed in accordance with the design approved by the director and shall have a minimum of two compartments with fittings designed for grease retention. C. The grease interceptor shall be installed at a location where it shall be at all times easily accessible for inspection, cleaning, and removal of accumulated grease. D. An access manhole, with a minimum diameter of 24 inches, shall be provided over each grease interceptor chamber and each sanitary tee. The access manholes shall extend at least to finished grade and be designed and maintained to prevent water inflow or infiltration. The manholes shall also have readily removable covers to facilitate inspection, grease removal and wastewater sampling activities.
( Ord. 4683 § 1, 2008 )