§ 907.2.9.4 — Automatic smoke detection system

San Francisco Administrative Code (2026 S-96: through Ordinance 133-26, File No. 260686, approved July 23, 2026, effective August 23, 2026) · SF Fire Code § 907.2.9.4

Corpus is an independent public-information project, not the official City of San Francisco website. Stable reference: corpuslaw.us/code/5ce71250-926a-4da3-a8c6-ca9e20260593

907.2.9.4. Automatic smoke detection system.

An automatic smoke detection system that activates the occupant notification system in accordance with Section 907.5 shall be installed throughout all interior corridors serving sleeping units. Exceptions: 1. An automatic smoke detection system is not required in buildings that do not have interior corridors serving sleeping units and where each sleeping unit has a means of egress door opening directly to an exit or to an exterior exit access that leads directly to an exit. 2. An automatic smoke detection system is not required in buildings when all of the following conditions are met: (a) The building is equipped throughout with a supervised automatic sprinkler system installed in accordance with Section 903.3.1.1 or 903.3.1.2. (b) The notification appliances will activate upon sprinkler water flow; and (c) At least one manual pull station is installed in an approved location.