§ 12.60.220: Numeric sizing criteria for treatment systems.

(a) Treatment best management practices for regulated projects shall incorporate the following hydraulic sizing design criteria to treat stormwater runoff. (1) Volume Hydraulic Design Basis. Treatment best management practices whose primary mode of action depends on volume capacity shall be designed to treat stormwater runoff equal to: (A) The maximized stormwater quality capture volume for the area, based on historical rainfall records, determined using the formula and volume capture coefficients set forth in Urban Runoff Quality Management, WEF Manual of Practice No. 23/ASCE Manual of Practice No. 87 (1998), pages 175 through 178 (e.g., approximately the eighty-fifth percentile twenty-four-hour storm runoff event); or (B) The volume of annual runoff required to achieve eighty percent or more capture, determined in accordance with the methodology set forth in Section 5 of the CASQA Stormwater Best Management Practices Handbook, New and Redevelopment (2003), or most recent edition, using local rainfall data. (2) Flow Hydraulic Design Basis. Treatment best management practices whose primary mode of action depends on flow capacity shall be sized to treat: (A) Ten percent of the fifty-year peak flow rate; or (B) The flow of runoff produced by rain equal to at least two times the eighty-fifth percentile hourly rainfall intensity for the applicable area, based on historical records of hourly rainfall depths (for Sunnyvale this is equivalent to 0.17 inches per hour); or (C) The flow of runoff resulting from rain equal to at least two-tenths of an inch per hour intensity. (3) Combination Flow and Volume Design Basis. Treatment systems that use a combination of flow and volume capacity shall be sized to treat at least eighty percent of the total runoff over the life of the project, using local rainfall data.

( Ord. 3213-23 § 1 )

Ask a question about Sunnyvale law

Corpus searches the Sunnyvale sections it holds and shows the ones that match, with their citations. Free, no sign-in.