§ 812.2.14 — Top plate. [Geological]

Municipal Code, City of Torrance, California · Torrance Municipal Code § 812.2.14

Corpus is an independent public-information project, not the official City of Torrance website. Stable reference: corpuslaw.us/code/783e128e-9dc6-4bca-9d20-e23660661aee

§ 812.2.14: Top plate. [Geological]

Exception of Section R602.3.2 and Table R602.3.2 of the 2025 Edition of the California Residential Code is amended to read as follows: Exception: In other than Seismic Design Category D0, D1 or D2, a single top plate used as an alternative to a double top plate shall comply with the following: 1. | The single top plate shall be tied at corners, intersecting walls, and at in-line splices in straight wall lines in accordance with Table R602.3.2. 2. | The rafters or joists shall be centered over the studs with a tolerance of not more than 1 inch (25 mm). 3. | Omission of the top plate is permitted over headers where the headers are adequately tied to adjacent wall sections in accordance with Table R602.3.2. [image]