§ 812.2.17 — Bracing requirements based on seismic design category. [Geological]
Municipal Code, City of Torrance, California · Torrance Municipal Code § 812.2.17
Corpus is an independent public-information project, not the official City of Torrance website. Stable reference: corpuslaw.us/code/f334039c-3667-4317-bbec-dc453100f07a
§ 812.2.17: Bracing requirements based on seismic design category. [Geological]
Table R602.10.4 of the 2025 Edition of the California Residential Code is amended to read as follows: [image] a. | Adhesive attachment of wall sheathing, including Method GB, shall not be permitted in Seismic Design Categories C, D0, D1 and D2. b. | Applies to panels next to garage door opening where supporting gable end wall or roof load only. Shall only be used on one wall of the garage. In Seismic Design Categories D0, D1 and D2, roof covering dead load shall not exceed 3 psf. c. | Garage openings adjacent to a Method CS-G panel shall be provided with a header in accordance with Table R602.7(1). A full-height clear opening shall not be permitted adjacent to a Method CS-G panel. d. | Method CS-SFB does not apply in Seismic Design Categories D0, D1 and D2. e. | Method applies to detached one- and two-family dwellings in Seismic Design Categories D0 through D2 only. f. | Methods GB and PCP braced wall panel h/w ratio shall not exceed 1:1 in SDC D0, D1 and D2. Methods LIB, DWB, SFB, PBS, HPS, and PFG are not permitted in SDC D0, D1 and D2. g. | Use of stapes in braced wall panels shall be prohibited in SDC DO, D1 and D2.