§ 14.12.210 — Tanks—Location
Code of Ordinances, City of Westminster, California (eCode360 WE5033 publication; scraped 2026-11-22) · Westminster Code of Ordinances § 14.12.210
Corpus is an independent public-information project, not the official City of Westminster website. Stable reference: corpuslaw.us/code/d57f936c-3681-4d13-80fb-9122f10f3cae
§ 14.12.210: Tanks—Location.
No tank shall be erected within twenty-five feet of any steam boiler or open flame; or at any location which is not in accordance with the following table (the measurements to be taken from the shell of the tank): LOCATION OF TANKS Capacity of Tank (42 Gal. Barrels) | Distance from Nearest Tank (Feet) | Distance from all other Structures or Buildings, and from the Nearest Line of Adjoining Property which May Be Built Upon (Feet) 1 | to | 266 | 2 | 8 267 | to | 720 | 3 | 10 721 | to | 1,600 | 5 | 15 1,601 | to | 2,884 | 5 | 15 2,885 | to | 5,031 | 7 | 20 5,032 | to | 10,200 | 7 | 20 10,201 | to | 15,000 | 10 | 25 15,001 | to | 23,500 | 15 | 30 23,501 | to | 40,000 | 20 | 40 40,001 | to | 70,000 | 25 | 50 70,001 | to | 95,000 | 30 | 60 95,001 | to | 135,000 | 40 | 80 Over | 135,000 | | 60 | 120
( Prior code § 3330.20 )