Sec. 42-68. - IFC - Section 503.2.1 Dimensions.
Section 503.2.1. Dimensions, is hereby amended in its entirety to read as follows: "503.2.1 Dimensions. Fire apparatus access roads shall have an unobstructed width of not less than 24 feet, exclusive of shoulders, except for approved security gates in accordance with Section 503.6, and an unobstructed vertical clearance of not less than thirteen (13) feet six (6) inches (4115 mm)."
(Ord. No. 4922, § 3, 3-24-2026)