§ 42-77 — IFC - Section 507.5.1.1 Hydrant for standpipe systems
Code of Ordinances of the City of Arvada, Colorado (Supp. No. 67: codified through Ordinance No. 4932, enacted May 5, 2026) · Arvada Code of Ordinances § 42-77
Corpus is an independent public-information project, not the official City of Arvada website. Stable reference: corpuslaw.us/code/8786bda5-6566-4f40-a6cb-6c9db0182dd7
Sec. 42-77. - IFC - Section 507.5.1.1 Hydrant for standpipe systems.
Section 507.5.1.1 Hydrant for standpipe systems, is hereby amended in its entirety to read as follows: "507.5.1.1 Hydrant for automatic sprinkler systems and standpipe systems. Buildings equipped with an automatic sprinkler system in accordance with Section 903.3.1.1 or Section 903.3.1.2 and/or standpipe system installed in accordance with Section 905 shall have a fire hydrant within 100 feet (30 480 mm) of the fire department connections along a fire apparatus access road. Exception: The distance shall be permitted to exceed 100 feet where approved by the fire code official to a maximum of 150 feet."
(Ord. No. 4922, § 3, 3-24-2026)