Sec. 42-90. - IFC - Section 903.4.3 Alarms.
Section 903.4.3. Alarms, is hereby amended in its entirety to read as follows: "903.4.3. Alarms. An approved audible/visual alarm device, located on the exterior of the building in an approved location, shall be connected to each automatic sprinkler system. Such sprinkler waterflow alarm devices shall be activated by waterflow equivalent to the flow of a single sprinkler of the smallest orifice size installed in the system. Where a fire alarm system is installed, actuation of the automatic sprinkler system shall actuate the building fire alarm system and cause notification as set forth in Section 907.5. When buildings have multiple tenant spaces notification devices shall be installed in accordance with Section 907.5 in each tenant space."
(Ord. No. 4922, § 3, 3-24-2026)