Sec. 22-105. - Section G2417.4.1 amended; test pressure.
Sec. G2417.4.1 of the residential code is amended to read as follows: G2417.4.1 Test pressure. The test pressure to be used shall be not less than 1½ times the proposed maximum working pressure, but not less than 10 psig (20 kPa gauge), for a minimum of 15 minutes, irrespective of design pressure. For medium pressure gas and welded gas lines, the minimum test pressure shall be 60 psig for a minimum of 30 minutes. Where the test pressure exceeds 125 psig (862 kPa gauge), the test pressure shall not exceed a value that produces a hoop stress in the piping greater than 50 percent of the specified minimum yield strength of the pipe.
(Code 1994, § 16.06.270; Ord. No. 47, 2016, §§ 1(exh. A), 2(exh. B), 12-20-2016)