For AI agents: read the machine-readable documentation index at /llms.txt or the single-file full reference at /llms-full.txt.

§ 22-49 — Section 1608.2 amended; ground snow loads

Municipal Code of the City of Greeley, Colorado (Codified through Ordinance No. 16, 2026, enacted April 21, 2026 (Supp. No. 6, Update 1)) · Greeley Municipal Code § 22-49

Corpus is an independent public-information project, not the official City of Greeley website. Stable reference: corpuslaw.us/code/3a03e74f-167f-42e2-836c-b20a6c06e7f5

Sec. 22-49. - Section 1608.2 amended; ground snow loads.

Sec. 1608.2 of the building code is amended to read as follows: 1608.2 Ground snow loads. The ground snow load (pg) shall equal 30 pounds per square foot (psf) in accordance with Colorado Design Snow Loads Report, published by the Structural Engineers Association of Colorado (dated April 2016). The design roof snow load values shall be determined from section 1608 of the IBC (including all applicable factors, and loading and drifting considerations of chapter 7 of ASCE 7), however, in no case shall the final design roof snow load be less than a uniformly distributed load of 20 psf.

(Code 1994, § 16.04.195; Ord. No. 47, 2016, §§ 1(exh. A), 2(exh. B), 12-20-2016)

Ask a question about Greeley law

Corpus searches the Greeley sections it holds and shows the ones that match, with their citations. Free, no sign-in.