Sec. 14.04.510. - Pressure-reducing valve.

Where the service water pressure to a building is expected to exceed 90 PSI, a water pressure reducing valve with strainer shall be installed at owner/builder expense just downstream of the building's main valve, so as to be accessible. The valve shall provide for pressure adjustment within the range of 55 to 90 PSI. The valve shall conform to the requirement of product standard ASSE (2) 1003 (American Society of Sanitary Engineering). Exemptions to this chapter are service lines to sill cocks, outside hydrants, and main supply risers to buildings where pressure from the main does not exceed 60 psi at the fixture branches or at individual fixtures.

(Code 1993, § 14.04.510; Code 2009, § 14.04.510; Ord. No. O-84-77, § 1; Ord. No. O-93-33, § 33)