Sec. 16.06.360. - Section G2417.4.1 amended; test pressure.
Section G2417.4.1 of the International Residential Code is revised by replacing the first sentence with the following: The test pressure to be used shall not be less than 1½ times the proposed maximum working pressure , and not less than 10 psig (69 kPa gauge)."
(Ord. No. O-2026-24, § 1, 6-9-2026)