§ 16.32.610 — Section B101.1 added; scope
Code of Ordinances of the City of Longmont, Colorado (Codified through Ordinance No. O-2026-39, enacted June 23, 2026 (Supp. No. 9)) · Longmont Code of Ordinances § 16.32.610
Corpus is an independent public-information project, not the official City of Longmont website. Stable reference: corpuslaw.us/code/760acbaa-19a0-4c84-afbe-3a4fb826f2c3
Sec. 16.32.610. - Section B101.1 added; scope.
Section B101.1 of International Fire Code is amended by addition of the following section: B101.2 Hydraulic Calculations. Whereby the supply is capable of supplying the required fire flow for the fire protection for properties within its jurisdiction, the minimum flow and duration requirements for the water distribution system shall be 2,000 gallons per minute for two hours for one-and two-family dwellings and 3,500 gallons per minute for three hours for all other buildings. The procedure for determining fire-flow requirements for buildings shall be in accordance with the City's adopted fire code as amended.
(Ord. No. O-2026-31, § 1, 6-9-2026)