For AI agents: read the machine-readable documentation index at /llms.txt or the single-file full reference at /llms-full.txt.

§ 16.32.360 — Section 907.1.3 amended; equipment

Code of Ordinances of the City of Longmont, Colorado (Codified through Ordinance No. O-2026-39, enacted June 23, 2026 (Supp. No. 9)) · Longmont Code of Ordinances § 16.32.360

Corpus is an independent public-information project, not the official City of Longmont website. Stable reference: corpuslaw.us/code/a9363bb9-95af-40ab-a46f-a17cc2c014ea

Sec. 16.32.360. - Section 907.1.3 amended; equipment.

Section 907.1.3 of the International Fire Code is deleted in its entirety and replaced with the following: 907.1.3. Equipment. Systems and components shall be listed and approved for the purpose for which they are installed. Only addressable fire alarm panels will be approved. Exception: Fire alarm panels that can transmit individual specific initiating device information. 907.1.3.1. Combination fire and security panels. A fire alarm system shall not be used for any purpose other than fire protection or control of fire protection systems. Combination fire and security panels are not permitted. 907.1.3.2. Fire alarm system wiring. All fire alarm wiring shall be red jacketed wiring listed and approved for fire alarm systems.

(Ord. No. O-2026-31, § 1, 6-9-2026)

Ask a question about Longmont law

Corpus searches the Longmont sections it holds and shows the ones that match, with their citations. Free, no sign-in.