For AI agents: read the machine-readable documentation index at /llms.txt or the single-file full reference at /llms-full.txt.

§ 16.32.260 — Section 901.6 amended; administration of installation acceptance testing

Code of Ordinances of the City of Longmont, Colorado (Codified through Ordinance No. O-2026-39, enacted June 23, 2026 (Supp. No. 9)) · Longmont Code of Ordinances § 16.32.260

Corpus is an independent public-information project, not the official City of Longmont website. Stable reference: corpuslaw.us/code/fd942965-c84a-4b4a-a293-34fbba2c0ef8

Sec. 16.32.260. - Section 901.6 amended; administration of installation acceptance testing.

Section 901.6 of the International Fire Code is amended by the addition of the following: Section 901.6.1. Installation acceptance testing for automatic fire sprinkler system tenant finish permit. The addition, modification, or deletion of 20 or more sprinkler heads requires a hydrostatic test of 50 psi above static system pressure for the period of two hours. Exception: A hydrostatic test of 50 psi above static is not required for separate permits issued for the same project limited to 19 or less sprinkler heads.

(Ord. No. O-2026-31, § 1, 6-9-2026)

Ask a question about Longmont law

Corpus searches the Longmont sections it holds and shows the ones that match, with their citations. Free, no sign-in.