Sec. 16.32.260. - Section 901.6 amended; administration of installation acceptance testing.
Section 901.6 of the International Fire Code is amended by the addition of the following: Section 901.6.1. Installation acceptance testing for automatic fire sprinkler system tenant finish permit. The addition, modification, or deletion of 20 or more sprinkler heads requires a hydrostatic test of 50 psi above static system pressure for the period of two hours. Exception: A hydrostatic test of 50 psi above static is not required for separate permits issued for the same project limited to 19 or less sprinkler heads.
(Ord. No. O-2026-31, § 1, 6-9-2026)