§ 16.32.280 — Section 903.2.11.1 amended; basements
Code of Ordinances of the City of Longmont, Colorado (Codified through Ordinance No. O-2026-39, enacted June 23, 2026 (Supp. No. 9)) · Longmont Code of Ordinances § 16.32.280
Corpus is an independent public-information project, not the official City of Longmont website. Stable reference: corpuslaw.us/code/6ee6635a-82bc-4d4b-b299-d58dc54cbe04
Sec. 16.32.280. - Section 903.2.11.1 amended; basements.
Section 903.2.11.1 of the International Fire Code is amended by the deletion of 903.2.11.1.3 and replaced with the following, and amended with the addition of 903.2.11.1.4: 903.2.11.1.3. Basements. Where any portion of a basement is located more than 50 feet (15,240 mm) from openings required by section 903.2.11.1, or where walls, partitions, or other obstructions are installed that restrict the application of water from hose streams, the basement shall be equipped throughout with an approved automatic sprinkler system. Exception: Exterior access or openings to basement approved by fire code official. 903.2.11.1.4. Buildings greater than 12,000 square feet. An automatic sprinkler system shall be provided throughout all buildings where the fire area exceeds 12,000 square feet, or where the combined fire areas on all floors, including mezzanines and basements, exceed 24,000 square feet. Exception: Occupancies in Group F-2.
(Ord. No. O-2026-31, § 1, 6-9-2026)