Sec. 16.32.330. - Section 905.2 amended; installation standard.

Section 905.2 of the International Fire Code is deleted in its entirety and replaced with the following: 905.2. Installation standard. Standpipe systems shall be installed/designed as an automatic wet standpipe with a 500 gpm at 100 psi at the two hydraulic most demanding hose outlets in accordance with this section and NFPA 14. Fire department connections for standpipe systems shall be in accordance with section 912. Exception: Automatic Dry Standpipe may be approved by the fire code official.

(Ord. No. O-2026-31, § 1, 6-9-2026)