Sec. 16.32.240. - Section 901.4.7.1 replaced; access.
Section 901.4.7.1 of the International Fire code is deleted in its entirety and replaced with the following: Section 901.4.7.1 Access. An unobstructed working space around automatic fire sprinkler risers, fire pumps, controllers, and fire alarm panels. measuring not less than 36 inches wide and 80 inches high shall be maintained at all times. Where located in a fire pump or automatic sprinkler system riser room, the door shall be permitted to be locked provided that the key is always available. Exception: Other clearances may be approved by the fire code official.
(Ord. No. O-2026-31, § 1, 6-9-2026)