Sec. 10-271. - Heating facilities.

(a) Facilities required. Heating facilities shall be provided in structures as required by this section. (b) Hotel/motel occupancies. Hotel and motel units shall be provided with heating facilities capable of maintaining a room temperature of 68°F (20°C) in all habitable rooms, bathrooms and toilet rooms. Cooking appliances shall not be used, nor shall portable unvented fuel-burning space heaters be used, as a means to provide required heating. (c) Occupy-able work spaces. Indoor occupy-able work spaces shall be supplied with heat to maintain a minimum temperature of 65°F (18°C) during the period the spaces are occupied. (1) Exceptions: a. Processing, storage and operation areas that require cooling or special temperature conditions. b. Areas in which persons are primarily engaged in vigorous physical activities. (d) Room temperature measurement. The required room temperatures shall be measured three feet (914 mm) above the floor near the center of the room and two feet (610 mm) inward from the center of each exterior wall.

(Ord. No. 3403, § 1, 9-13-16)