8.44.060 - Foam generators—When required.

On every premises upon which there shall be one or more aboveground tanks used for the storage of explosive and flammable liquids having a total capacity in excess of seventy thousand (70,000) gallons, there shall be maintained one or more foam generators in which the foam-generating chemicals hereinbefore provided may in case of fire be used on such premises by the fire department. The fire chief shall determine the size and number of generators which shall be maintained on every premises upon which generators are required under this chapter. No generator which shall not be approved by the fire chief shall be deemed to comply with the provisions of this chapter.

(Ord. dated 12/21/92 § 75(b); prior code § 11-135)