§ 8.44.110 — Foam delivery systems—Requirements

Bridgeport, Connecticut Municipal Code (Supp. No. 24, Update 2: codified through Ordinance dated July 6, 2026) · Bridgeport Municipal Code § 8.44.110

Corpus is an independent public-information project, not the official City of Bridgeport website. Stable reference: corpuslaw.us/code/7023365d-e87d-4e03-93fa-c781c94051d7

8.44.110 - Foam delivery systems—Requirements.

The foam delivery system required by Section 8.44.100 shall meet the following requirements: A. Delivery of Foam Solutions. Such foam delivery system shall be of such type that foam solutions will be delivered through appropriate piping to a delivery chamber attached to the shell at the top of the tank in which the foam solutions will be united to produce the fire-extinguishing foam described in this chapter and from which the foam so produced will be discharged through a discharge outlet into the tank interior. B. Delivery Chambers. The delivery chambers shall be securely attached to the shell of the tank at or near the top thereof and shall be so located and connected thereto as to preclude the possibility of the tank contents flowing into the delivery chamber and the solution pipelines thereto and to prevent the discharge of foam below the oil surface of the tank. Such chambers shall be so fastened to the tank shell that they will not be seriously damaged in the event of explosion within the tank which may damage or destroy the roof of the tank. C. Discharge Outlets of Delivery Chambers. The discharge outlet of such delivery chamber may enter the tank interior through the shell of the tank at the top thereof or through the roof. If such outlet shall enter the tank through the roof, an approved flashing joint shall be provided at the point of such entrance so that, in the event of explosion within the tank which shall damage the roof, such outlet will remain intact and uninjured. D. Vapor Seals. There shall be maintained on the discharge outlet of each delivery chamber an effective and durable vapor seal which shall be readily ruptureable under light foam pressure to permit the discharge of foam into the tank interior but which shall prevent the explosive and flammable vapors within the tank from entering into such delivery chamber. E. Means of Inspection of Delivery Chambers. All delivery chambers shall be provided with a suitable means of ready inspection to permit proper maintenance and the inspection and replacement of the vapor seals required in this chapter. F. Deflector Plates, etc. The discharge outlet of each delivery chamber shall be equipped on the inside of the tank with an approved deflector plate or other means of diverting or directing the flow of foam so as to eliminate undue splashing or agitation of the surface of the oil. G. Number of Delivery Chambers. Tanks not exceeding sixty-five (65) feet in diameter shall be provided with at least one delivery chamber, tanks exceeding sixty-five (65) feet but not exceeding one hundred seventeen and six-tenths (117.6) feet in diameter shall be provided with at least two delivery chambers and tanks exceeding one hundred seventeen and six-tenths (117.6) feet in diameter shall be provided with at least three delivery chambers. Where more than one delivery chamber is required or provided for any tank, they shall be equally spaced about such tank. H. Solution Pipelines—Construction. Solution pipelines shall extend from such delivery chamber along the shell of the tank to the ground and shall extend from the side of the tank to a point outside of the dike wall surrounding the protected tank and shall then either directly or through solution mains extend to the foam-generating plant of such system. I. Foam-Generating Plant—Location and Requirement. On every premises upon which a foam delivery system is required by this chapter, there shall be maintained a foam-generating plant in which foam-generating solutions shall be produced and from which such solutions shall by piping be directed to the tanks protected by said system. Such plant may be a separate structure of fireproof construction or may be a room on the ground level of a building of fireproof construction, provided such building shall not be devoted in whole or in part to the storage or handling of explosive or flammable liquids. Such plant shall be sufficiently removed from any tank on such premises as to be subjected to a minimum of exposure from fire thereon. Unless peculiar circumstances shall, in the opinion of the fire chief, require, there shall be but one such foam-generating plant for any premises. The location of such plant and the construction and condition thereof shall be such as shall be approved by the fire chief. J. Foam-Generating Plant—Construction and Equipment. The foam generators required under this chapter shall be maintained in the foam-generating plant and shall be so arranged and set up therein and so connected to the water supply lines and to the solution lines or mains as to be ready at all times for instant use. Such connections shall be such that the generators may be readily detached so as to be available for use at other points on such premises as necessity in case of fire may require. An adequate water supply of sufficient volume and pressure to permit the use of all of such generators and to produce such quantity of foam solution as may be required for the tanks protected by such system shall be provided for such plant. Appropriate valves shall be provided within the plant which will permit the supply of water to be directed to one or more or all of such generators. The foam-generating chemicals and other generating equipment required under this chapter shall, so far as possible, be maintained in such plant so as to be available for instant use in case of fire with a minimum of handling. K. Water Pressure and Capacity of Equipment. If in the opinion of the fire chief the pressure of the water supply to any foam-generating plant shall be inadequate for the proper and efficient operation of the foam-generating and delivery system on said premises, there shall be provided and maintained thereon such electrically operated pumping equipment as will increase the water pressure to the degree which shall be required by the fire chief. The equipment of every foam-generating plant, which shall be maintained pursuant to this chapter, shall be capable of delivering at least three-quarters of a gallon of foam per minute for each square foot of the largest oil surface to be protected by such system, and in no event less than fifty (50) gallons of foam per minute. L. Size and Location of Solution Mains and Valves. The size of the solution mains and pipelines of the foam delivery system shall be such as to eliminate undue friction and to supply the tanks protected by such foam delivery system with an adequate supply of foam-generating solutions with a maximum of efficiency and effectiveness. If along such solution mains or pipelines, there shall be valves designed to control the supply of foam solution from the foam-generating plant to particular tanks, such valves shall be located outside of any dike wall and shall be removed from the tank to be supplied through such valves a distance equivalent at least to the diameter of such tank and in any event not less than fifty (50) feet therefrom and from any other tank. Unless peculiar circumstances shall, in the opinion of the fire chief, require, solution mains and pipelines outside of dike walls need not be buried below the surface of the ground if their location is such that they will not readily be exposed to damage. The size of all solution mains and pipelines, and the installation thereof, and the size, design and location of all valves shall be such as shall meet with the approval of the fire chief. M. Foam Hydrants—Requirements. There shall be provided along the solution mains or pipelines of foam delivery systems an adequate number of foam hydrants to which hose lines may be attached for the application of foam to fires of explosive or flammable liquids outside of tanks or upon and into tanks which are not protected by such foam delivery system. If upon such premises there shall be any loading rack, or if there shall be any wharf, dock or pier from which explosive or flammable liquids shall be received from vessels and shall by piping or otherwise be delivered therefrom to the tanks on such premises, solution mains or pipelines shall be so laid that one or more foam hydrants may be provided at or near such loading rack and on or near such wharf, dock or pier. The number, size, construction and location of such foam hydrants shall be such as shall be approved by the fire chief; and such hydrants shall have such attachments and fittings that the hose lines of the fire department may be readily attached thereto.

(Ord. dated 12/21/92 § 75(b); prior code § 11-140)

Ask a question about Bridgeport law

Corpus searches the Bridgeport sections it holds and shows the ones that match, with their citations. Free, no sign-in.