§ 13-124 — Tanks located near buildings having cellars or basements
Code of Ordinances of the City of Hartford, Connecticut (Supp. No. 119: codified through Ordinance of May 11, 2026) · Hartford Code of Ordinances § 13-124
Corpus is an independent public-information project, not the official City of Hartford website. Stable reference: corpuslaw.us/code/310d0e41-dad3-4eb6-8cba-e92b0e4d0910
Sec. 13-124. - Tanks located near buildings having cellars or basements.
A tank containing volatile inflammable fluid, if located within ten (10) feet of a building having a cellar or basement and not placed below the level of the floor of such cellar or basement, shall be protected from leakage in such manner as shall be directed by the fire chief and to his satisfaction. No tank having a capacity of one hundred ten (110) gallons or more shall be located less than ten (10) feet from a cellar wall. No tank having a capacity of five hundred (500) gallons or more shall be located less than fifteen (15) feet from a cellar wall. No tank having a capacity of one thousand (1,000) gallons or more shall be located less than twenty (20) feet from a cellar wall.
(Code 1977, § 13-121)