Sec. 13-127. - Same—Pipes.

Each underground storage tank under this division shall be provided with a fill pipe, a draught pipe, a vent pipe and a gauge pipe. The opening to the gauge pipe shall be protected to the satisfaction of the fire chief. When a tank is located under the building, the fill pipe and the vent pipe must run to the outside of such building. The vent pipe shall be of galvanized wrought iron not less than one and one-quarter (1¼) inches in diameter. It shall run from the top of the tank and shall terminate not less than twelve (12) feet above the surface of the ground and not less than ten (10) feet measured horizontally and vertically from any window or other opening in any adjacent building. It shall terminate with a double gooseneck opening downward. Such opening shall be protected by a brass wire screen not coarser than thirty-by-thirty mesh or the equivalent.

(Code 1977, § 13-124)