Sec. 7-83. - Fire mains.
Fire main taps connected to the public water system shall be sized for, and serve, only the building for which they were installed and shall not be shared with or used by other buildings. Fire mains shall be constructed of class 52 ductile iron pipe (DIP) or other pipe UL listed for underground fire main use, as approved by the fire rescue services department. Fire main taps may be shared only where a single fire pump is shared in accordance with section 7-84. Fire mains shall only enter a building above ground through an exterior wall, and shall not run under foundations or footers. In high-rise buildings (as defined in the Florida Fire Prevention Code and the Florida Building Code), fire main configurations shall be in accordance with the Florida Building Code.
(Ord. No. 5726, § 2, 2-25-25)