Sec. 7-85. - Fire protection system closet.

(1) A fire protection system closet ("closet") shall be provided for all buildings and structures equipped with a fire alarm or fire sprinkler protection. (a) The closet shall house the fire sprinkler system riser, all appropriate control valves, all appropriate flow and tamper switches, the fire alarm system control panel, annunciator panel, annunciator map/legend and the transmitter/control unit. As provided in the FFPC and NFPA 72, portions of the fire alarm system may be located elsewhere in the building subject to approval by the fire rescue services department. (b) The annual fire alarm registration and copies of the most recent fire alarm, and fire sprinkler, inspection reports shall be posted in the closet. (c) The closet shall not be used for storage and shall not be used for any other electrical, plumbing or mechanical equipment. (d) The minimum size of the closet shall be 2 feet deep by 4 feet wide, which may be increased to accommodate the provided equipment. (e) The closet shall be separated from all other portions of the building with 1 hour fire resistive construction as a minimum. The closet shall be located along an outside wall, at grade, with access from an outside swinging door, which need not be fire rated. (f) The door to the closet shall be labeled with a sign that reads "Fire Protection Closet" or "FACP Room." The closet shall be kept locked at all times. A key keeper box approved by the fire rescue services department shall be installed on the outside wall, within 3 feet of the closet. The key keeper box shall be installed 42 inches to 48 inches above grade. The key box shall contain a key to access the fire alarm control closet, the fire alarm control room, and have all the keys necessary to control the fire alarm system, and keys to access other areas of the building including, but not limited to, electrical rooms, fire pump room, elevator machine, roof, and rooms containing any hazardous materials. The property owner may provide as many additional keys as may be desired to access all interior areas of the building. The key box shall be sized appropriately such that all keys, access cards, fobs, and other contents (if required) fit inside in a manner so that the fire rescue services department personnel are able to open and close the door of the key box with ease. (g) A weatherproof horn/strobe or speaker/strobe shall be installed directly above the key box at a height so that it can be easily seen upon approach to the area. (h) The closet shall be designed and constructed to provide and maintain a climate-controlled temperature of no greater than 80 degrees Fahrenheit. (2) A closet is not required to be included in high rise buildings and other buildings where a fire pump room and a fire command room are required. A closet is not required in single family homes and duplexes.

(Ord. No. 5726, § 2, 2-25-25)

Ask a question about Boca Raton law

Corpus searches the Boca Raton sections it holds and shows the ones that match, with their citations. Free, no sign-in.