§ 10-12 — Amendments to NFPA 1 Section 18.5.5 of the Florida Fire Prevention Code

Code of Ordinances, City of Gainesville, Florida (Supp. No. 64, Update 1: codified through Ordinance No. 2024-740, adopted November 6, 2025) · Gainesville City Code § 10-12

Corpus is an independent public-information project, not the official City of Gainesville website. Stable reference: corpuslaw.us/code/523a5669-8bf7-4edb-9a4d-4dc8ee520eb4

Sec. 10-12. - Amendments to NFPA 1 Section 18.5.5 of the Florida Fire Prevention Code.

NFPA 1 Section 18.5.5 is amended by adding the following: When required, protective posts shall meet the following minimum requirements: a. Be a minimum of three-inch diameter schedule 40 PVC or three-inch diameter steel pipe set in 36 inches depth of concrete at least 15 inches in diameter. The inside of the pipe shall be filled with solid concrete; b. Be located at least three feet from the fire hydrant; c. Extend above ground to a minimum of fire hydrant height; and d. Be spaced a minimum of three linear feet to protect the fire hydrant.

(Ord. No. 002251, § 1, 9-9-02; Ord. No. 080841, § 5, 5-7-09; Ord. No. 120051, § 3, 9-6-12; Ord. No. 140495, § 5, 3-5-15)