Sec. 9-78. - Fire hydrants.

All new fire hydrants shall be compression type with the bottom valve opening to be five and one-fourth (5¼) inches in diameter. They shall be erected so as to have the center of the steamer connection a minimum of eighteen (18) inches above the crown of the nearest roadway or eighteen (18) inches above the surrounding ground and with the steamer opening of four and one-half (4½) inches (maximum height) in size with four (4) National Standard Threads per inch. All fire hydrants shall be "traffic type" to breakaway upon impact. The fire hydrant main body valve shall open against the flow and shall close with the flow.

(Ord. No. 97-35, § 1, 6-4-97)