16.40.050.15.2. - Above-ground tanks, not elevated.

Above-ground tanks that do not meet the elevation requirements of section 16.40.050.15.3. shall: 1. Be permitted in flood hazard areas (Zone A/AE) other than coastal high hazard areas provided the tanks and their foundations are anchored and otherwise designed by a professional engineer, and constructed and installed to prevent flotation, collapse or lateral movement resulting from hydrodynamic, hydrostatic, and all flood-related and other loads during conditions of the design flood, including the effects of buoyancy assuming the tank is empty and the effects of flood-borne debris. Loads on tanks exposed to flooding shall be determined assuming at least one and one-half times the potential buoyant and other flood forces acting on an empty tank and shall take into consideration the eroded ground elevation. 2. Not be permitted in coastal high hazard areas (Zone V/VE).

(Ord. No. 743-L, § 1, 7-15-2021)