§ 50-4 — Use of sprinkler systems in multifamily structures
Code of Ordinances of the City of Kennesaw, Georgia (Codified through Ordinance No. 2026-06, enacted March 2, 2026. (Supp. No. 37)) · Kennesaw Municipal Code § 50-4
Corpus is an independent public-information project, not the official City of Kennesaw website. Stable reference: corpuslaw.us/code/816776be-b4c9-45fc-9655-c42ce29d049b
Sec. 50-4. - Use of sprinkler systems in multifamily structures.
(a) Applicability. This section applies only to multifamily residential structures with a maximum of three stories in height. A story is defined as that portion of a building included between the upper surface of the floor and the upper surface of the floor or roof next above. (b) System requirements. In structures described in subsection (a) of this section, a combination fire protection sprinkler system shall be allowed. A combination fire protection system, for purposes of this section, means that the sprinkler system and the domestic water system utilize the same (common) service water supply pipe to the premises. Such system shall comply with the following: (1) Any calculations of pipe size shall be based on a 24-hour chart and must be approved by the authority having jurisdiction prior to permitting the sprinkler system. (2) No antifreeze solution or any other additive shall be allowed in any combination sprinkler system. (3) When a dead-end system is used, the sprinkler system shall be isolated from the domestic water system by not less than a dual checkvalve backflow preventer that conforms to ASSE standard 1024, and provides the flow requirements of the system without exceeding the allowable pressure drop of the standard or the system, whichever is less. A union and full-port shutoff valve, acceptable to the city, shall be installed on both sides of the backflow preventer to facilitate removal for test and repair. If sprinkler system pressure exceeds 120 psi a pressure reducing valve must be used. Exception: In low pressure areas only, where residual pressure or flow gallons per minute do not meet minimum requirements, one head must flow minimum 18 gallons per minute with a 41 psi residual, and two heads must flow minimum 30 gallons per minute with a 30 psi residual, unless otherwise U.L. listed "A" circulating system may be used. The terminal end of the sprinkler supply shall be tied directly into the supply to a regularly used water closet or other approved fixture. Branch lines shall not exceed 25 feet on any circulating system. The backflow preventer requirement is waived on such systems. (4) When the dual check and shutoff valves are installed outside the building, they shall not be buried in earth, but shall be installed in such manner as meter boxes and protected from freezing, at a location acceptable to the city. The top of the protective housing shall extend one-half inch above the finished landscaping. (5) All shutoffs in the sprinkler system shall be secured with lock and key in the open position. A sign on valves should read "Fire department should be notified when valves are turned off and when turned back on." All shutoffs shall be readily accessible at all times. (6) A supply line to the sprinkler system shall be tapped off the water service line at a point that would be downstream (customer side of meter) of any backflow preventer the water purveyor might subsequently require in the service line to contain the domestic system from the public mains. (7) All sprinkler heads used shall be U.L. listed, fast acting domestic sprinkler heads for either pendant or side wall use. (8) The spacing of pendant heads shall be a maximum of eight feet from any wall unless U.L. listed for greater coverage. (9) The spacing of side wall heads shall be in accordance with U.L. listings. (10) Sprinkler heads are not required in bathrooms, closets, foyers, halls, or attics. All other areas require sprinkler heads, including drive-in garages and basements, finished or unfinished. Exception: Meet hazardous area hourly fire rating for drive-in garages. (11) All mechanical rooms (furnace, water heater) shall have 135 to 165 degree commercial head with maximum three-eighths-inch orifice. (12) Dropped escutcheons shall be used if sprinkler head is obstructed by light fixtures or beams. The builder may use additional heads for areas where obstructions block the spray pattern. (13) When ceiling fans are used, sprinkler heads shall be located so fan escutcheon does not interfere with the pattern. Relocation of head shall still conform to spacing requirements. If sprinkler head location exceeds spacing requirements, additional heads shall be used. (14) All spacing of sprinkler heads, in relation to obstruction, such as fireplaces and heaters, shall be to sprinkler head manufacturers' requirements. (15) A minimum three-fourths-inch flow water meter is required if individual water meters are used. (16) All sprinkler piping in unheated areas shall be protected from freezing. (17) An accepted water flow switch with bell is required. Both shall be accessible for checking and repair. (18) Each system shall have an accessible test drain valve. (19) If the sprinkler system is designed for more than one living unit and separate electric service is used for each unit, the alarm switch with bell shall be on the house electric meter. (20) All condominiums shall have the following wording in the recorded declaration of covenants and a copy of the document shall be provided to the county fire marshal and city building inspector: a. Sprinkler system: In the event that any unit should be equipped with a sprinkler system, nothing shall be hung from the sprinkler heads comprising a part of the system, nor shall any such sprinkler heads be painted, covered, or otherwise changed, tampered with or altered. b. Prior to any alteration, amendment, modification or change thereof, he/they will submit such alteration, amendment, modification or change to the Cobb County fire marshal for his approval and agree to comply with all domestic sprinkler requirements of the fire marshal. (21) The installer shall be a licensed fire protection sprinkler company or a licensed plumber. (c) Exceptions to building code. When a structure is equipped with a sprinkler system meeting the requirements of subsection (b) of this section, or meeting the requirements of NFPA section 13d, the following exceptions to the building code may be allowed: (1) Fire department access may be extended from 50 feet from back of parking area to face of building to a maximum of 125 feet to face of building. (2) Fire wall requirements: a. For buildings up to 8,000 square feet per floor, no fire wall is required. b. For buildings up to 10,000 square feet per floor, a two-hour fire wall to the underside of roof deck is required at the approximate center. c. For buildings over 10,000 square feet per floor, a four-hour fire wall extending up to 36 inches above the roof surface and out flush with the roof overhang is required every 8,000 square feet. (3) Standard one-half-inch gypsum wallboard may be substituted for the five-eighths-inch type X gypsum wallboard relating to one-hour tenant separation walls. (4) Standard one-half-inch gypsum wallboard may be substituted for the five-eighths-inch type X gypsum wallboard and five-eighths-inch plywood may be substituted for three-fourths-inch plywood relating to one-hour floor-ceiling assemblies. (5) Fee simple townhouses may have a one-hour rated party walls in lieu of two-hour rated party walls. (6) Attic smoke stops at 3,000 square feet will be allowed in lieu of smoke stops between every unit. (7) Exit travel may be extended to a maximum of 35 feet in lieu of the existing 20 feet. (8) Tenants may travel by other tenants' doors and windows without those doors and windows being rated. (9) Interior finish shall be class C or better. (10) One-hour rating of walls and doors of hazardous areas will not be required. (11) Unless otherwise specified within this Code, all other requirements of applicable codes of the city shall be complied with. (12) Certification of flow must be acceptable to the authority having jurisdiction.
(Code 1986, § 4-2-4)
Ask a question about Kennesaw law
Corpus searches the Kennesaw sections it holds and shows the ones that match, with their citations. Free, no sign-in.