§ 50-5 — Amendments pertaining to multifamily housing, three or more units, three stories or less

Code of Ordinances of the City of Kennesaw, Georgia (Codified through Ordinance No. 2026-06, enacted March 2, 2026. (Supp. No. 37)) · Kennesaw Municipal Code § 50-5

Corpus is an independent public-information project, not the official City of Kennesaw website. Stable reference: corpuslaw.us/code/da6438f4-1f68-4c28-a90e-c6a676b195d1

Sec. 50-5. - Amendments pertaining to multifamily housing, three or more units, three stories or less.

The following provisions apply to all multifamily housing comprising three or more units, and of three stories or less: (1) Water mains and fire hydrants on private property. a. Water mains and fire hydrants shall be installed in accordance with the plans approved by the county fire marshal. b. Water mains and fire hydrants shall be installed and approved by the county water and sewer system under water pressure and ready for firefighting before any combustible framing begins. (2) Accessibility for firefighting equipment. a. Reasonable accessibility shall be provided to all buildings for firefighting equipment, including ladder trucks on multiple-story projects. A minimum of ten feet level ground on all sides of the building shall be considered reasonable for rescue ground ladders. Reasonable accessibility for ladder trucks shall be determined by the county fire department. b. Access to the job site shall consist of roads or streets being finished to the extent that curbing and base coat must be applied before combustible construction starts, and shall be maintained throughout construction operations. (3) Partitions for multifamily dwellings. a. Every dwelling unit shall be separated from every other dwelling unit and hallways and breezeways by partitions and floor-ceiling assemblies having a fire resistance rating of not less than one hour, and be completely firestopped at each floor and ceiling level. The one-hour walls of the hall, corridor, or breezeway may stop at the ceiling if this ceiling is five-eighths-inch type X sheetrock and a smokestop of one layer of one-half-inch regular sheetrock on the hall side of each hall wall and is continued to the roof deck above. 1. Exception no. 1: When the one-half hour floor-ceiling assembly has at least one layer of five-eighths-inch type X sheetrock on the bottom side, resilient channels will not be required. 2. Exception no. 2: If the ceiling of the uppermost unit is one layer five-eighths-inch type X sheetrock, the one-hour partition shall be allowed to stop at the ceiling. b. Buildings having only a single row of units shall have smokestops between each unit of not less than one-half-inch gypsum with tape covered with one coat of joint compound installed in a manner to prevent the passage of smoke and gases to other units. Exception: Buildings having units back to back, where roof trusses are perpendicular to the tenant separation, will have a smokestop to separate every two units. c. Doors to hallways and breezeways shall have a minimum fire rating of 20 minutes in a 20-minute wood frame with a closer (spring hinge closers will be acceptable only after approval of county fire marshal's office) in buildings from one to three stories. Door openings within 15 feet horizontally of a single exit stair shall have a three-fourths-hour door, with closer, in a steel frame. d. For buildings closer than 20 feet to other buildings, each exterior wall facing the building shall have a minimum fire rating of one hour with no openings. Note: Fee simple townhouses require two-hour separation per Standard Building Code. (4) Fire wall requirements for multifamily dwellings. a. No building shall have more than 6,000 square feet per floor between four-hour fire walls. b. Fire wall definition: Fire walls shall be self-supporting from the foundation, and shall extend through and 36 inches from combustible roofs and flush with outside of roof overhang. Fire walls need not extend through fire resistive roof decks. Fire walls shall be four-hour rated. Certification of block will be required. There shall be no unprotected openings in fire walls. (5) Requirements for early fire detection system and exits in multifamily dwellings. a. An approved single station smoke detector, powered by the house electrical service, shall be installed in every living unit. There shall be additional detectors located in each exit corridor every 30 feet. For the purpose of this subsection, an outside breezeway or balcony is not a corridor. b. Exiting in multifamily dwellings shall be as follows: Every living unit shall have access to at least two separate exits, remote from each other as required by the Life Safety Code. 1. Exception no. 1: Any living unit which has an exit directly to the street or yard at ground level or by way of an outside stairway or an enclosed stairway with fire resistance rating of one hour or more serving that apartment only and not communicating with any floor below the level of exit discharge or other area not a part of the apartment served may have a single exit. 2. Exception no. 2: Buildings of any height with not more than four living units per floor with a smokeproof tower or outside stair in accordance with the requirements of the Life Safety Code as the exit, immediately accessible to all apartments served thereby, may have a single exit. "Immediately accessible" means a travel distance of 20 feet maximum from the door of an apartment to the door of an open air vestibule or balcony leading to a smokeproof tower. 3. Exception no. 3: Any building three stories or less in height with no floor below the level of exit discharge or, in case there is such a floor, with the street floor construction of at least one hour fire resistance, may have a single exit, under the following conditions: i. The stairway is completely enclosed with a partition having a fire resistance rating of at least one hour with self-closing three-fourths-hour fire protection rated doors protecting all openings between the stairway enclosure and the building. ii. The stairway does not serve any floor below the level of exit discharge. iii. All corridors serving as access to exits have at least a one-hour fire resistance rating. iv. There is not more than 20 feet of travel distance to reach an exit from the entrance door of any living unit. (6) Protection of hazardous areas. All hazardous areas shall be separated from other parts of the building by construction having a fire resistance of at least one hour, with three-fourths-hour labeled door, with steel frame and closer; spring hinge closers will be acceptable only after approval of the county fire marshal's office. These areas shall include, but are not limited to, boiler or furnace rooms, general storage and maintenance shops, or parking or storage of motorized vehicles. They do not include furnaces or hot water heaters located within individual units which serve only that unit nor do they include storage rooms for individual units. (7) Control of flame spread. The flame spread on carpet, wall covering, paneling, or wood in multifamily dwellings shall be as follows: a. Vertical exits and corridors and breezeways shall have a class B (26—75) flame spread rating. b. The interior of the units shall be class C flame spread rating (76—200). (8) Control of openings through floors. a. Any opening through floors from one unit to another for piping or plumbing must be sealed with lightweight concrete or other permanently attached noncombustible material. b. Any opening through any floor for any purpose shall be sealed in like manner. c. The double wall furnace vent must be sealed tight at each floor level and at the ceiling level of the top unit. The double wall furnace vent is not required to be enclosed in the attic space; proper clearance must be maintained. d. If a combustion air vent pipe is required for combustion air to the furnace, it shall extend up through the floor-ceiling assembly and into the attic 18 inches above the ceiling with proper firestopping at each floor level. e. Each attic space shall have an attic access provided. This door cannot be in a closet, unless it is a walk-in closet. f. If an opening is made in a smokestop wall, it must be self-closing; screen door type spring is acceptable. (9) Chimney chases. a. Exterior chase. A chimney chase located on an exterior wall will require five-eighths-inch fire-rated gypsum wallboard on the inside of the chase on the house side only, through the top of chimney. An exterior chimney chase will require a firestop at each floor level. b. Interior chase. Chases located on an interior wall must be sealed inside and outside with five-eighths-inch fire-rated gypsum wallboard through the top of the chimney. An interior chase will require a firestop at each floor and one at the ceiling level. This firestop shall be a minimum of one-half-inch plywood with proper metal firestop around each flue. All clearances must comply with both the manufacturer's recommendations and the city building inspector's requirements. Exception: Alternative method of protection for exterior and interior chases: 1. Exterior chases: The exterior walls of the chase may be wood studs covered with five-eighths-inch type X sheetrock on the inside up 48 inches from the floor. The front wall of the chase on the floor level where a fireplace is located shall have metal studs extending from the floor to the ceiling, covered with one layer of five-eighths-inch type X sheetrock. Firestops will be required at floor, ceiling and attic levels. 2. Interior chases: Metal studs shall be installed on all four walls of the chase and shall extend through the roof to the top of the chimney. The metal studs must be covered on the outside with one layer of five-eighths-inch type X sheetrock and be completely sealed from the rest of the building with no combustibles inside the chase. 3. If there is no fireplace above, firestopping at floor-ceiling levels may be omitted if there are no combustibles inside the chase. If there is a fireplace on the floor above, the bottom of the floor joist must be covered with five-eighths-inch type X sheetrock with metal firestops installed around the flue. (10) Firebox and fireplace openings. a. The firebox is to be installed on a wooden platform with one-half-inch hearth above the subfloor. b. The woodwork shall not be placed within six inches of a fireplace opening. The woodwork above and projecting more than 1½ inches from a fireplace opening shall not be placed less than 12 inches from the top of a fireplace opening.

(Code 1986, § 4-2-5)

Ask a question about Kennesaw law

Corpus searches the Kennesaw sections it holds and shows the ones that match, with their citations. Free, no sign-in.