Sec. 7-385. - Required backflow prevention assemblies for containment, fire protection systems.
(a) A reduced pressure principle backflow prevention assembly shall be installed on all new and existing fire protection systems which the administrative authority determines to have any of the following: (1) Direct connections from public water mains with an auxiliary water supply on or available to the premises for pumper connection. (2) Interconnections with auxiliary supplies, such as reservoirs, rivers, ponds, wells, mills, or other industrial water systems. (3) Use of antifreezes or other additives in the fire protection system. (4) Combined industrial or domestic with high hazard and fire protection systems supplied from the public water mains only, with or without gravity storage or pump suction tanks. (5) Any other facility, connection, or condition which may cause contamination. (b) A double check valve assembly shall be required for all other fire protection systems. The double check valve shall be required on all new systems at the time of installation and on existing systems at the time that they are upgraded. (c) Submittal of proposed backflow prevention devices to the administrative authority does not relieve the designer or sprinkler contractor of the responsibility of submitting plans, including backflow prevention devices, to the fire marshal for approval.
(Code 2017, § 7-507; Ord. No. 2196, § 1, 6-23-1997)
Ask a question about Cedar Falls law
Corpus searches the Cedar Falls sections it holds and shows the ones that match, with their citations. Free, no sign-in.