§ 12.36 — Cross-Connection Control

Cedar Rapids, Iowa, Municipal Code (Supp. No. 25, Update 1: codified through Ordinance No. 025-26, passed July 28, 2026) · Cedar Rapids Municipal Code § 12.36

Corpus is an independent public-information project, not the official City of Cedar Rapids website. Stable reference: corpuslaw.us/code/bb65b6c5-383d-451d-b75e-2d9260b153ab

12.36 - Cross-Connection Control.

Purpose. The purpose is to safeguard potable water supplies by preventing backflow into public water systems. Administrative authority. For the purposes of this Chapter and Chapter 35 of this Code only, the administrative authority is the City Council acting through such persons or agencies the City Council shall designate. The administrative authority shall have the right to enter any property to inspect for possible cross-connections. The administrative authority may collect fees for the administration of this program. Said fees shall be set by City Council resolution. The administrative authority shall maintain records of cross-connection hazard surveys, and the installation, testing, and repair of all backflow-prevention assemblies installed for containment and isolation purposes. New water services. Plans shall be submitted to the administrative authority for review on all new water services in order to determine the degree of hazard. The administrative authority shall determine the type of backflow-prevention assembly required for containment based on the degree of hazard. The administrative authority shall require the installation of the appropriate backflow-prevention assembly for containment before the initiation of water service. There shall be a minimum requirement of a University of Southern California (USC) approved double check valve assembly on all properties classified commercial unless a determination is made by the administrative authority that a Reduced-Pressure Principal Assembly (RPZ) is required. Existing water services. Upgrades of existing water services shall be treated as new water services for the purposes of this Chapter and Chapter 35 of this Code. The administrative authority shall publish and make available to each customer a copy of the standards used to determine the degree of hazard. After publication of the standards, the administrative authority shall, in writing, notify customers whose premises are classified as single-family residential of the provisions of this Chapter and shall require compliance therewith. Within 6 months after publication of the standards, customers whose premises are not classified as single-family residential shall complete and return to the administrative authority a cross-connection hazard survey to be used to determine the type of containment device. The administrative authority shall, on the basis of information received from customers or gathered through on-premises investigations or surveys, determine the type of backflow-prevention assembly required for containment based on the degree of hazard. Within the time frame specified in writing by the administrative authority, the customer shall install a backflow-prevention assembly for containment required by the administrative authority. The administrative authority may inspect the premises to determine the degree of hazard. When high hazard cross-connections are found, the administrative authority shall, at its sole discretion: Develop a schedule of compliance which the customer shall follow; or Terminate the water service until a backflow-prevention assembly for containment required by the administrative authority has been installed. Failure of the administrative authority to notify a customer that they are believed to have a high hazard cross-connection and that they shall install backflow-prevention assemblies for containment in no way relieves a customer of the responsibility to comply with all requirements of this Section. Customer. The customer shall be responsible for ensuring that no cross-connections exist without approved backflow-prevention within their premises starting at the point of service from the public potable water system. The customer shall, at their own expense, cause installation, operation, testing, and maintenance of the backflow-prevention assemblies required by the administrative authority. The customer shall ensure the administrative authority is provided with copies of records of the installation and of all tests and repairs made to the backflow-prevention assembly on the approved form within 15 days after testing and/or repairs are completed. In the event of a backflow incident, the customer shall immediately notify the Water Division and the Cedar Rapids Building Department of the incident and take immediate action to confine the contamination or pollution. Required backflow-prevention assemblies for containment-water services. An airgap or an approved reduced-pressure principle backflow-prevention assembly is required for water services having one or more cross-connections that the administrative authority classifies as high hazard. An approved double check valve assembly is required for water services having no high hazard cross-connections but having one or more cross-connections that the administrative authority has classified as low hazard. Required backflow-prevention aassemblies for containment-fire protection systems. A reduced-pressure principle backflow-prevention assembly shall be installed on all new and existing fire protection systems that the administrative authority determines to have any of the following: Direct connections from public water mains with an auxiliary water supply on or available to the premises for pumper connection; Interconnections with auxiliary supplies such as reservoirs, rivers, ponds, wells, mills, or other industrial water systems; Use of antifreezes or other additives in the fire protection system; Combined industrial or domestic with high hazard and fire protection systems supplied from the public water mains only, with or without gravity storage or pump suction tanks; or Any other facility, connection, or condition which may cause contamination. A double check valve assembly will be required for all other fire protection systems. The double check valve shall be required on all new systems at the time of installation and on existing systems at the time that they are upgraded. Registration of backflow-prevention assembly technician. A backflow-prevention assembly technician registered by the State of Iowa shall include their registration number on all correspondence and forms required by this Chapter. Registered backflow-prevention assembly technician noncompliance. The registration of a technician will be recommended for revocation or suspension for a period of up to two years for noncompliance with this Chapter. Further action will be taken as prescribed by law to prevent further noncompliance. Any of the following conditions constitute noncompliance: Improper testing or repair of backflow-prevention assemblies; Improper reporting of the results of testing or of repairs made to backflow-prevention assemblies; Failure to meet registration requirements; Related unethical practices. Installation of backflow-prevention assemblies. The required backflow-prevention assemblies for containment shall be installed in horizontal plumbing immediately following the meter or as close to that location as deemed practical by the administrative authority. In any case, it shall be located upstream from any branch piping. Installation at this point does not eliminate the responsibility of the customer to protect the water supply system from containment or pollution between the backflow-prevention assembly and the water main. Reduced-pressure principle backflow-prevention assemblies shall be installed so as to be protected from flooding. Reduced-pressure principle backflow-prevention assemblies shall not be installed in underground vaults or pits. All backflow-prevention assemblies shall be protected to prevent freezing. Those devices used for seasonal services may be removed in lieu of being protected from freezing; however, the devices must be reinstalled and tested by a registered backflow-prevention assembly technician prior to service being reactivated. If hot water is used within the water system, thermal expansion shall be provided for when installing a backflow-prevention assembly for containment. Provisions shall be made to convey the discharge of water from reduced-pressure principle backflow-prevention assemblies to a suitable drain. No backflow-prevention assemblies shall be installed in a place where it would create a safety hazard, such as, but not limited to, over an electrical panel or above ceiling level. If interruption of water service during testing and repair of backflow-prevention assemblies for containment is unacceptable to the customer, another backflow-prevention assembly, sized to handle the temporary water flow need during the time of test or repair, should be installed in parallel piping. All such installation shall be at the customer's expense. All backflow-prevention assemblies shall be installed so that they are accessible for testing as stated in this Chapter and Chapter 35 of this Code. All shut-off valves shall conform with requirements of the current edition of the Manual of Cross-Connection Control (University of Southern California) for either ball gate valves or resilient seat gate valves at the time of installation. Ball valves shall be used on assemblies installed in piping 2 inches and smaller and resilient seat gate valves on assemblies installed in piping larger than 2 inches. Testing of backflow-prevention assemblies. Testing of backflow-prevention assemblies shall be performed by a registered backflow-prevention assembly technician. The costs of tests required in paragraphs (k)2-(k)5 of this subsection shall be borne by the customer. Backflow-prevention assemblies shall be tested upon installation and tested and inspected at least annually. Backflow-prevention assemblies that are in place but have been out of operation for more than three months shall be tested before being put back into operation. Backflow-prevention assemblies used in seasonal applications shall be tested before being put into operation each season. Any backflow-prevention assembly which fails a periodic test shall be repaired or replaced. When water service has been terminated for noncompliance, the backflow-prevention assembly shall be repaired or replaced prior to the resumption of water service. Backflow-prevention assemblies shall be retested by a registered backflow-prevention assembly technician immediately after repair or replacement. The administrative authority may require backflow-prevention assemblies to be tested at any time in addition to the annual testing requirement. The registered backflow-prevention assembly technician shall report the successful test of a backflow-prevention assembly to the customer and to the administrative authority on the form provided by the administrative authority within 15 days of the test. The administrative authority may require, at its own cost, additional tests of individual backflow-prevention assemblies as it shall deem necessary to verify test procedures and results. A fine shall be assessed to any property owner who fails to report within the required timeline the required test information on any backflow assembly. Continued failure to submit the proper report will result in termination of water service. Repair of backflow-prevention assemblies. All repairs to backflow-prevention assemblies shall be performed by registered backflow-prevention assembly technicians. The registered backflow-prevention assembly technician shall not change the design, material, or operational characteristics of a backflow-prevention assembly during repair or maintenance and shall use only original manufacturer replacement parts. The registered backflow-prevention assembly technician shall report the repair of a backflow-prevention assembly to the customer and to the administrative authority on the form provided by the administrative authority within 15 days of the repair. The report shall include the list of materials or replacement parts used. A fine shall be assessed to any property owner who fails to repair or replace a failed backflow assembly device immediately. Continued failure to repair will result in termination of water service. Customer noncompliance. The water service may be discontinued in the case of noncompliance with this Chapter and Chapter 35 of this Code. Noncompliance includes, but is not limited to, the following: Refusal to allow the administrative authority access to the property to inspect for cross-connections; Removal of a backflow-prevention assembly that has been required by the administrative authority; Bypassing of a backflow-prevention assembly that has been required by the administrative authority; Providing inadequate backflow prevention when cross-connections exist; Failure to install a backflow-prevention assembly that has been required by the administrative authority; Failure to test and/or properly repair a backflow-prevention assembly as required by the administrative authority; Failure to comply with the requirements of this chapter. (025-24)

Ask a question about Cedar Rapids law

Corpus searches the Cedar Rapids sections it holds and shows the ones that match, with their citations. Free, no sign-in.