Sec. 14-156. - Fire standards and inspections.
(a) Smoke detectors. A supervised smoke detection system shall be installed in all amusement houses in conformance with the fire code. When the amusement house is permanent, this smoke detection system shall either be cross zoned or shall utilize an approved verification system. Exception: In areas where the ambient conditions will cause a smoke detector to alarm, an approved alternate type of automatic detector shall be installed. (b) Sprinklers. An approved automatic sprinkler system complying with the Uniform Building Code standards 38-1 shall be installed in all amusement houses. When the amusement house is temporary or mobile, the sprinkler water supply may be an approved temporary means. Exception: An automatic sprinkler system is not required when the total floor area of a building containing an amusement house is less than 1,000 square feet and the travel distance from any point to an exit is less than 50 feet. (c) Fire protection system performance. Fire protection system performance shall be as follows: (1) Permanent amusement house. a. The activation of two cross zoned smoke detectors within a single protected area, a single smoke detector monitored by an alarm verification zone, the automatic sprinkler system or any other automatic fire alarm detection shall automatically: 1. Cause illumination of the means of egress with light of not less than one footcandle at the walking surface level; 2. Stop any conflicting or confusing sounds and visuals; and 3. Activate an approved directional exit marking that will become apparent in an emergency. b. Activation of any single smoke detector, the automatic sprinkler system or any other automatic fire detection device shall immediately sound an alarm at the building at a constantly attended location from which emergency action can be initiated including the capacity of manual initiation of subsection (c)(1)a of this section. (2) Temporary amusement house. a. Provide a constantly attended location that has the capacity to manually initiate: 1. Illumination of the entire area including all exitways; 2. Cessation of any conflicting sounds and visuals; and 3. Activate or illuminate an approved directional exit marking that will become apparent in an emergency. b. Provide an alarm system that will sound an alarm at the attended location upon the activation of any of the fire detection devices being used.
(C85, § 6-100; O.11,393, 11,526; C91, § 6-100)
Ask a question about Des Moines law
Corpus searches the Des Moines sections it holds and shows the ones that match, with their citations. Free, no sign-in.