§ 46-457 — Emergency power

Municipal Code of the City of Des Moines, Iowa (Supp. No. 38, Update 3: codified through Ordinance No. 16,577, adopted August 24, 2026) · Des Moines Municipal Code § 46-457

Corpus is an independent public-information project, not the official City of Des Moines website. Stable reference: corpuslaw.us/code/7e2f185f-3b3a-4f04-bcb1-dfab22e2cd67

Sec. 46-457. - Emergency power.

Insert new section 1201.4 with the following language: Section 1201.4 Shutdown of Energy Systems. In addition to the requirements of NFPA 110 for a remote manual stop, a switch of an approved type shall be provided to disable the power source. The switch shall be provided at an approved location. Insert new section 1201.5 with the following language: Section 1201.5 Secondary Power Supply Signs. Main electrical disconnects and main breaker panels supplied by the generator shall be provided with approved signs. Additionally, doors accessing power systems shall be provided with approved signs. Approved signs shall contain the word CAUTION in black letters at least 2 inches (50 mm) high on a yellow background. Such warning signs shall be placed so as to be readily discernible.

(O.15,546, 15,860, 16,521)