Sec. 46-469. - Automatic fire sprinkler requirements.
Delete section 903.2.1.1 and insert in lieu thereof the following new section: 903.2.1.1 Group A-1. An automatic sprinkler system shall be provided throughout stories containing Group A-1 occupancies and throughout all stories from the Group A-1 occupancy to and including the levels of exit discharge serving that occupancy where one of the following conditions exists: 1. The fire area exceeds 6,000 square feet (557.5 m 2 ). 2. The fire area has an occupant load of 300 or more. 3. The fire area is located on a floor other than a level of exit discharge serving such occupancies. 4. The fire area contains a multiple-theater complex. Delete section 903.2.1.2 and insert in lieu thereof the following new section: 903.2.1.2 Group A-2. An automatic sprinkler system shall be provided throughout stories containing Group A-2 occupancies and throughout all stories from the Group A-2 occupancy to and including the levels of exit discharge serving that occupancy where one of the following conditions exists: 1. The fire area exceeds 1,500 square feet (139 m 2 ). 2. The fire area has an occupant load of 50 or more. 3. The fire area is located on a floor other than a level of exit discharge serving such occupancies. Delete section 903.2.1.3 and insert in lieu thereof the following new section: 903.2.1.3 Group A-3. An automatic sprinkler system shall be provided throughout stories containing Group A-3 occupancies and throughout all stories from the Group A-3 occupancy to and including the levels of exit discharge serving that occupancy where one of the following conditions exists: 1. The fire area exceeds 6,000 square feet (557.5 m 2 ). 2. The fire area has an occupant load of 300 or more. 3. The fire area is located on a floor other than a level of exit discharge serving such occupancies. Delete section 903.2.1.4 and insert in lieu thereof the following new section: 903.2.1.4 Group A-4. An automatic sprinkler system shall be provided throughout stories containing Group A-4 occupancies and throughout all stories from the Group A-4 occupancy to and including the levels of exit discharge serving that occupancy where one of the following conditions exists: 1. The fire area exceeds 6,000 square feet (557.5 m 2 ). 2. The fire area has an occupant load of 300 or more. 3. The fire area is located on a floor other than a level of exit discharge serving such occupancies. Delete section 903.2.2 and insert in lieu thereof the following new section: 903.2.2 Group B. An automatic sprinkler system shall be provided throughout buildings containing a Group B occupancy where one of the following conditions exists: 1. A Group B fire area exceeds 12,000 square feet (557.5 m 2 ). 2. A Group B fire area is located more than three stories above grade plane. 3. The combined area of all Group B fire areas on all floors, including any mezzanines, exceeds 24,000 square feet (1115 m 2 ). 4. As required by 903.2.2.1 & 903.2.2.2 Delete section 903.2.3 and insert in lieu thereof the following new section: 903.2.3 Group E. An automatic sprinkler system shall be provided throughout stories containing Group E occupancies and throughout all stories from the Group E occupancy to and including the levels of exit discharge serving that occupancy where one of the following conditions exists: 1. The fire area exceeds 1,500 square feet (139 m 2 ). 2. The fire area has an occupant load of 50 or more. 3. The fire area is located on a floor other than a level of exit discharge serving such occupancies. Delete section 903.2.4 and insert in lieu thereof the following new section: 903.2.4 Group F-1. An automatic sprinkler system shall be provided throughout all buildings containing a Group F-1 occupancy where one of the following conditions exists: 1. A Group F-1 fire area exceeds 6,000 square feet (557.5 m 2 ). 2. A Group F-1 fire area is located more than three stories above grade plane. 3. The combined area of all Group F-1 fire areas on all floors, including any mezzanines, exceeds 12,000 square feet (1115 m 2 ). 4. A Group F-1 occupancy is used to manufacture lithium-ion or lithium metal batteries. 5. A Group F-1 occupancy is used to manufacture vehicles, energy storage systems, or equipment containing lithium-ion or lithium metal batteries where the batteries are installed as part of the manufacturing process. Delete section 903.2.7 and insert in lieu thereof the following new section: 903.2.7 Group M. An automatic sprinkler system shall be provided throughout buildings containing a Group M occupancy where one of the following conditions exists: 1. A Group M fire area exceeds 6,000 square feet (557.5 m 2 ). 2. A Group M fire area is located more than three stories above grade plane. 3. The combined area of all Group M fire areas on all floors, including any mezzanines, exceeds 12,000 square feet (1115 m 2 ). Delete section 903.2.9 and insert in lieu thereof the following new section: 903.2.9 Group S-1. An automatic sprinkler system shall be provided throughout all buildings containing a Group S-1 occupancy where one of the following conditions exists: 1. A Group S-1 fire area exceeds 6,000 square feet (557.5 m 2 ). 2. A Group S-1 fire area is located more than three stories above grade plane. 3. The combined area of all Group S-1 fire areas on all floors, including any mezzanines, exceeds 12,000 square feet (1115 m 2 ). 4. A Group S-1 fire area used for the storage of commercial motor vehicles where the fire area exceeds 5,000 square feet (464 m 2 ). 5. A Group S-1 fire area used for the storage of lithium-ion or lithium metal powered vehicles where the fire area exceeds 500 square feet (46.4 m 2 ). Delete section 903.2.9.1 and insert in lieu thereof the following new section: 903.2.9.1 Repair garages. An automatic sprinkler system shall be provided throughout all buildings used as repair garages in accordance with section 406.8 of the International Building Code, as shown: 1. Buildings not more than one story above grade plane, with a fire area containing a repair garage exceeding 3,500 square feet (325 m 2 ). 2. Buildings with repair garages servicing vehicles parked in basements. 3. A Group S-1 fire area used for the repair of commercial motor vehicles where the fire area exceeds 3,500 square feet (325 m 2 ). 4. A Group S-1 fire area used for the storage of lithium-ion or lithium metal powered vehicles where the fire area exceeds 500 square feet (46.4 m 2 ) Delete section 903.2.11.1.3 and insert in lieu thereof the following new section: 903.2.11.1.3 Basements. Where any portion of a basement is located more than 75 feet (22,860 mm) from openings required by section 903.2.11.1, the basement shall be equipped throughout with an approved automatic sprinkler system. Delete section 903.3.1.2 and insert in lieu thereof the following new section: 903.3.1.2 NFPA 13R sprinkler systems. Automatic sprinkler systems in Group R occupancies shall be installed throughout in accordance with NFPA 13, unless allowed to be sprinklered in accordance with NFPA 13D by the International Building Code. Delete section 903.4.3 and insert in lieu thereof the following new section: 903.4.3 Alarms. An approved weather proof audible device suitable for outdoor use with 110 candela visual signal shall be connected to every automatic sprinkler system. The audible device shall be a horn style device that produces a "tri-tone" signal in accordance with NFPA 72. Such sprinkler water-flow alarm devices shall be activated by water flow equivalent to the flow of a single sprinkler of the smallest orifice size installed in the system. A weather-proof horn-strobe shall be installed on a separate Notification Appliance Circuit (NAC) or shall be installed as an addressable device that is able to function as if the alarm is on a separate NAC. This alarm shall be included in any battery and voltage drop calculations. This device shall only operate on active water flow from the sprinkler system, shall not be able to be silenced, and shall continue to be active until water flow has stopped and the fire alarm panel has been reset. The alarm device(s) shall be provided on the exterior of the building in an approved location adjacent to each fire department connection. Where a fire alarm system is installed, actuation of the automatic sprinkler system shall actuate the building fire alarm system.
(O.15,546, 15,860, 16,318, 16,521)
Ask a question about Des Moines law
Corpus searches the Des Moines sections it holds and shows the ones that match, with their citations. Free, no sign-in.