§ 46-471 — Fire alarm requirements
Municipal Code of the City of Des Moines, Iowa (Supp. No. 38, Update 3: codified through Ordinance No. 16,577, adopted August 24, 2026) · Des Moines Municipal Code § 46-471
Corpus is an independent public-information project, not the official City of Des Moines website. Stable reference: corpuslaw.us/code/2a0236cd-2e77-4f7a-87c9-dfdf60ab68f4
Sec. 46-471. - Fire alarm requirements.
Insert new section 907.1.4 with the following language: 907.1.4 FACP (Fire Alarm Control Panels). Each building shall have no more than 1 FACP. Installation of fire alarm panel shall be not exceed six feet in height measured from the floor to the top of the unit. Exception: Suppression system releasing panels are not required to meet the height requirement or the limitation in the number of panels.
(O.15,546, 16,333, 16,521)