Sec. 46-472. - Smoke and heat vent requirements.

Delete section 910.2.1 and insert in lieu thereof the following new section: 910.2.1 Group F-1 or S-1. Smoke and heat vents installed in accordance with section 910.3 or a mechanical smoke removal system installed in accordance with section 910.4 shall be installed in buildings and portions thereof used as a Group F-1 or S-1 occupancy having more than 30,000 square feet (2787 m 2 ) of undivided area. In occupied portions of a building equipped throughout with an automatic sprinkler system in accordance with 903.3.1.1, where the upper surface of the story is not a roof assembly, a mechanical smoke removal system in accordance with section 910.4 shall be installed. Exception: Group S-1 aircraft repair hangars.