§ 46-473 — Fire pump requirements
Municipal Code of the City of Des Moines, Iowa (Supp. No. 38, Update 3: codified through Ordinance No. 16,577, adopted August 24, 2026) · Des Moines Municipal Code § 46-473
Corpus is an independent public-information project, not the official City of Des Moines website. Stable reference: corpuslaw.us/code/c5de03c7-7100-41a7-b369-0b83de850366
Sec. 46-473. - Fire pump requirements.
Delete section 914.3.1.2 and insert in lieu thereof the following new section: 914.3.1.2 Water supply to required fire pumps. Required fire pumps shall be supplied by connections to a minimum of two water mains located in different streets. Separate supply piping shall be provided between each connection to the water main and the pumps. Each connection and the supply piping between the connection and the pumps shall be sized to supply the flow and pressure required for the pumps to operate. Exception: Two connections to the same main shall be permitted provided the main is valved such that an interruption can be isolated so that the water supply will continue without interruption through at least one of the connections.
(O.15,546, 16,521)