Sec. 46-498. - Fuel fired appliances.
Insert new section 1108.1 with the following language: 1108.1 Protection of Fuel Fired Appliances. Where required or upon notification from the fire code official an existing building or tenant space containing a fuel fired appliance(s) shall be protected with 1 hour rated construction enclosure or a limited area sprinkler system complying with section 903.3.8. Exception: Buildings protected by an approved automatic fire sprinkler system complying with section 903.3.1.1 or 903.3.1.2. Insert new section 1108.2 with the following language: 1108.2 CSST Bonding Requirements in Rental Dwellings. All rental dwellings shall be bonded in accordance with sections NFPA 54, unless deemed technically infeasible by the fire code official. Insert new section 1108.3 with the following language: 1108.3 CSST Bonding Requirements for Alterations, Repairs, or Additions. For other than rental dwelling units, where alterations, repairs or additions requiring a permit to occur, CSST shall be bonded in accordance with NFPA 54, unless deemed technically infeasible by the fire code official.
(O.15,546, 15,860, 16,318, 16,521)