Sec. 46-510. - High-piled storage.
Insert new section 3202.2 with the following language: 3202.2 Definitions. SPECULATIVE BUILDING. A Group S, F, or M occupancy having an interior clear height greater than 12 feet (3657 mm) where high-piled storage may accrue and the client leasing or the occupant owner does not know the commodity that will be stored or the method of storage. Insert new section 3206.2.2 with the following language: 3206.2.2 Speculative building. Group S, F, and M speculative buildings that have an interior clear height greater than 12 feet where high piled storage may accrue shall comply with this chapter. Insert new section 3206.4.2 with the following language: (1) 3206.4.2 Sprinkler design. a. 3206.4.2.1 General. The design of automatic sprinkler systems for the protection of Group F, H, M, or S occupancies containing high-piled storage or high-challenge commodities over an area equal to or greater than 2,500 ft. 2 (232 m 2 ) and designed for the protection of hazardous materials stored more than one pallet high in Group F, H, M, or S occupancies, shall be in accordance with this section. This section does not apply to miscellaneous storage within the scope of NFPA 13. b. 3206.4.2.2 Requirements for all plan submittals. See sections 903.1.9 and 3201.3 for plan submittal requirements. c. 3206.4.2.3 Minimum design requirements for speculative warehouses. The design of the automatic sprinkler system for speculative warehouses shall be based on storage of a cartoned Class A non-expanded plastic to the available storage height. The storage height shall be determined by subtracting 48 inches as measured from the highest point of the roof for ESFR and 30 inches for area density applications. d. 3206.4.2.4 Minimum requirements for client leased or occupant-owned warehouses. 1. The design of an automatic sprinkler system for client leased or occupant owned buildings containing high piled storage shall be based on the requirements of NFPA 13. The responsible Fire Protection Contractor shall perform a survey of the building to determine commodity classification, storage configuration, building height, and other information related to the development of an appropriate sprinkler system design. The Contractor shall also make reasonable efforts to meet with the building owner or operator to understand seasonal or customer related fluctuations to the stored commodities, storage height, and configuration. 2. The sprinkler design shall be based on the most demanding requirements determined through the on-site survey and discussions with the building owner or operator. Technical Report shall clearly define the basis for determining the commodity and sprinkler design selection, along with how the commodities will be isolated or separated, and the referenced design document(s), including NFPA 13 or the current applicable Factory Mutual Data Sheets. If a specific fire test is used as the basis of design, a copy of the fire test report shall be provided at the time of plan review. e. 3206.4.2.5 Required information at plan submittal. All plans, hydraulic calculations and technical reports shall be submitted with the plan submittal form. The individual submitting the design package shall ensure that all of the required information requested on the plan submittal form is included. f. 3206.4.2.6 Minimum plan information requirements. In addition to the requirements of NFPA 13, the following information shall be included in the plans or technical report. 1. 3206.4.2.6.1 Classes I through IV and Group A plastic commodities. i. An owner's certificate in accordance with NFPA 13. The design criteria, e.g., NFPA 13, Factory Mutual Data Sheet, or a specific fire test report. ii. A Water Supply Flow & Pressure Test Report performed within 90 days of the plan submittal. iii. The type of design, e.g., Control Mode Density/Design Area Method; Specific Application Control Mode Method; Suppression Mode Method, including appropriate code references. iv. A description of the stored commodities and how the commodity classification was determined. v. A layout of the proposed storage arrangement. If the storage is in racks, a plan and elevation detail illustrating rack heights, flue dimensions, and arrangement. This detail is not required for speculation warehouses. vi. The aisle dimensions between each storage array. vii. If a high challenge commodity is separated using fire-resistive construction, the boundary of the fire-resistive construction shall be illustrated. viii. A data sheet for the backflow preventer. If a data sheet is not available, the design professional shall include a statement addressing the minimum required pressure loss. ix. A data sheet for each installed automatic sprinkler. x. A data sheet for each pipe hanger used to hang or support the sprinkler piping. xi. If a fire pump will be installed or used, the manufacturer's factory test curve shall be included in the submittal. xii. A cross-section view illustrating obstructions to the ceiling sprinklers, e.g., lights, structural members, cable trays, electrical bus ducts, and HVAC ductwork. 2. 3206.4.2.6.2 Hazardous materials. In addition to the requirements of this section, the following information shall be included in a hazardous materials technical report: i. A hazardous materials inventory statement. ii. For flammable & combustible liquids, an analysis of the miscibility of Class I liquids, the size and type of the packaging, the packaging materials of construction, and if the containers have a pressure relieving mechanism. iii. For Level 2 or 3 aerosols, a statement indicating that the aerosols are cartoned or uncartoned. g. 3206.4.2.7 Identification of sprinkler system capabilities and limitations. A label shall be permanently installed at or adjacent to each sprinkler riser. When a building contains more than four risers, the sign shall be located at an approved location inside the building. The minimum sign dimension is 6-inches (152 mm) high by 4-inches (101 mm) wide. The sign shall specify the capabilities and limitations of the automatic sprinkler system. The sign shall include the following information: 1. The design base or basis, including the edition used. 2. A statement indicating if the sprinkler design is control mode density area method, control mode specific application, suppression mode, or any combination thereof. 3. When used, all of the storage conditions stipulated NFPA 13 for Special Designs. 4. The maximum storage height. 5. The minimum required aisle width. 6. If storage is in racks, the maximum rack width and minimum transverse and longitudinal flue widths. 7. Storage Capabilities: Commodities designed to be protected by the automatic sprinkler system. 8. Limits on storage heights of idle wood and plastic storage. 9. Limits on storage heights of miscellaneous Group A plastic, tire, and rolled paper storage. 10. Locations where in-rack sprinklers are required. 11. Locations where horizontal and/or vertical barriers are required. 12. Information explaining the manufacturer, sprinkler identification number, k-factor, and operating temperature of the overhead sprinklers protecting the high-piled storage. 13. Fire Protection Contractor contact information. (2) The following example illustrates a suggested label or sign: Automatic Sprinkler System Capabilities & Limitations Stored Commodity | Class I water miscible flammable liquids in 1 & 5 gallon polyethylene containers in fiberboard cartons Design Documents | NFPA 13, 2013 edition & NFPA 30 Design Type | Control Mode, Density/Area Method Max. Storage Height | 25 feet Min. Aisle Width | 8 feet Max. Rack Width | 9 feet Flue Dimensions | Longitudinal: Min. 6 inches Transverse: Min. 3 inches System Capabilities | Class I-IV commodities, stored commodity, solid pile or palletized Group A plastics to 12 feet; rack storage of Group A plastics to 25 feet. Idle Pallets | 6 feet maximum storage height Tire Storage | 5 feet maximum storage height Rolled Paper Storage | 5 feet maximum storage height In-rack sprinklers | In-rack sprinklers are required at each of 3 rack tiers containing the stored commodity. In-rack sprinklers are Tyco/Central FS-B, 17/32" orifice, QR 155°F element, SIN TY0041 Horizontal Barriers | Required at each rack tier containing the stored commodity. Ceiling Sprinkler | Tyco ELO-231B, ¾" orifice, SR 286°F element, upright, SIN TY0030 FP Contractor | ABC Sprinkler Co. Designer: John Smith
(O.15,546, 15,860, 16,318, 16,521)
Ask a question about Des Moines law
Corpus searches the Des Moines sections it holds and shows the ones that match, with their citations. Free, no sign-in.