For AI agents: read the machine-readable documentation index at /llms.txt or the single-file full reference at /llms-full.txt.

§ 15-1.1 — International Fire Code—Amendments

Code of Ordinances of the City of Lewiston, Idaho (Codified through Ordinance No. 4973, enacted July 27, 2026. (Supp. No. 11)) · Lewiston Code of Ordinances § 15-1.1

Corpus is an independent public-information project, not the official City of Lewiston website. Stable reference: corpuslaw.us/code/312ec9a3-15b5-4124-9690-b2167adf60e8

Sec. 15-1.1. - International Fire Code—Amendments.

The 2018 International Fire Code, compiled by the International Code Council, adopted by section 15-1 of this Code, is hereby amended as follows: (1) Chapter 1, Sections 102.1 and 103.2, are hereby adopted as written in the International Fire Code. (2) Chapter 1, Section 102.5, is hereby amended to add the following: 3. Minimum requirements for unsprinklered single family homes and multiple family dwellings up to two (2) units as identified by the State of Idaho action (Idaho Code 39-4116(3)) shall be as provided for in the 2006 IFC/IRC/IBC for wall ratings and egress components. (3) Chapter 1, Section 102.6, is hereby amended to read as follows: 102.6 Historic buildings. The provisions of this code relating to the construction, alteration, repair, enlargement, restoration, relocation or moving of existing buildings or structures shall not be mandatory for existing buildings or structures identified and classified by the state or local jurisdiction as historic buildings where such buildings or structures do not constitute a distinct hazard to life or property and such buildings or structures shall be in accordance with the provisions of the International Existing Building Code as adopted by the City of Lewiston. Fire protection in designated historic buildings shall be provided with an approved fire protection plan as required in Section 1103.1.1 of this code. (4) Chapter 1, Section 102.7, is hereby amended to read as follows: 102.7 Referenced codes and standards. The codes and standards referenced in this code shall be the most recent editions of those that are listed in Chapter 80, and such codes and standards shall be considered to be part of the requirements of this code to the prescribed extent of each such reference and as further regulated in Sections 102.7.1 and 102.7.2. (5) Chapter 1, Section 104.1, is hereby amended to add the following: 104.1.1 Fire Chief's Authority. The fire chief is authorized to administer and enforce this code. Under the chief's direction, the fire department is authorized to enforce all ordinances of the jurisdiction pertaining to: a. The prevention of fires; b. The suppression or extinguishment of dangerous or hazardous fires; c. The storage, use and handling of hazardous materials; d. The installation and maintenance of automatic, manual and other private fire alarm systems and fire-extinguishing equipment; e. The maintenance and regulation of fire escapes; f. The maintenance of fire protection and the elimination of fire hazards on land and in buildings, and other property, including those under construction; g. The maintenance of means of egress; and h. The investigation of the cause, origin and circumstances of fire and unauthorized releases of hazardous materials, for authority related to control and investigation of emergency scenes, see Section 104.11. (6) Chapter 1, Section 105.1.1, is hereby amended to read as follows: 105.1.1 Permits required. A property owner or owner's authorized agent who intends to conduct an operation or business, or install or modify systems and equipment that are regulated by this code, or to cause any such work to be performed, shall first make application to the fire code official and obtain a permit if required by the authority having jurisdiction. (7) Chapter 1, Section 109, is hereby amended to read as follows: Sections 10-1(c) and 10-2(10) of the Lewiston City Code pertaining to the code board of appeals shall apply to the International Fire Code. (8) Chapter 1, Section 110.3.1, is hereby amended to read as follows: 110.3.1 Service. A notice of violation issued pursuant to this code shall be served upon the owner, the owner's authorized agent, operator, occupant, or other person responsible for the condition or violation either by: (a) personal service; (b) certified or first-class mail, addressed to the last known address; or (c) delivering the same to, and leaving it with, some person of responsibility upon the premises. If notice is hand-delivered, such notice shall be deemed delivered immediately. If notice is sent by certified or first-class mail, such notice shall be deemed delivered forty-eight (48) hours after depositing the same in the U.S. mail. For unattended or abandoned locations, a copy of such notice of violation shall be posted on the premises in a conspicuous place at or near the entrance to such premises, and such notice shall be deemed delivered twenty-four (24) hours after such notice is posted, and the notice of violation shall be mailed by certified mail with return receipt requested or a certificate of mailing to the last known address of the owner, the owner's authorized agent, or occupant. (9) Chapter 1, Section 110.3.4, is hereby amended to read as follows: 110.3.4 Unauthorized tampering. Signs, tags, or seals posted or affixed by the fire code official shall not be mutilated, destroyed, tampered with, concealed, or removed. Signs, tags, or seals shall only be removed by the fire code official. (10) Chapter 1, Section 110.4, is hereby amended to read as follows: 110.4 Violation penalties. In addition to the penalties set forth in Lewiston City Code § 10-2(8) pertaining to work commencing before permit issuance, persons who shall violate a provision of this code or shall fail to comply with any of the requirements thereof or who shall erect, install, alter, repair or do work in violation of the approved construction documents or directive of the fire marshal, or of a permit or certificate used under provisions of this code, shall be guilty of a misdemeanor, punishable as provided in Section 1-7 of the Lewiston City Code. Each day that a violation continues shall be deemed a separate offense. (11) Chapter 1, Section 112.4, is hereby amended to read as follows: 112.4 Failure to comply. Any person who shall continue any work after having been served with a stop work order, except such work as that person is directed to perform to remove a violation or unsafe condition, shall be guilty of a misdemeanor, punishable as provided in Lewiston City Code section 1-7. (12) Chapter 2, Section 202, is hereby adopted as written in the International Fire Code and amended to add the following: 202 General Definitions. Bedroom. See sleeping room. Sleeping Room. A room with a closet shall be considered a sleeping room regardless of its intended use by the current owner (i.e. den, office, study, media, sewing or exercise room, etc.). All sleeping rooms shall be provided with emergency escape and rescue openings and smoke alarms as required. (13) Chapter 3, Section 308.1.6.3, is hereby adopted as written in the International Fire Code. (14) Chapter 3, Section 312, is hereby amended to read as follows: 312.1 General. Vehicle impact protection required by this code shall be provided by posts that comply with Section 312.2 or by other approved physical barriers that comply with Section 312.3. 312.2 Posts. Guard posts shall comply with all of the following requirements: 1. Constructed of steel not less than four inches (4") in diameter and concrete filled. 2. Spaced not more than four feet (4') between posts on center. 3. Set not less than three feet (3') deep in a concrete footing of not less than a fifteen inch (15") diameter. 4. Set with the top of the posts not less than three feet (3') above ground. 5. Located not less than three feet (3') from the protected object. 312.3 Other Barriers. Physical barriers shall be a minimum of thirty-six inches (36") in height and shall resist a force of twelve thousand (12,000) pounds applied thirty-six inches (36") above the adjacent ground surface. Barriers, other than posts specified in Section 312.2, that are designed to resist, deflect or visually deter vehicular impact commensurate with an anticipated impact scenario shall be permitted where approved. (15) Chapter 3, Section 315.3.4, is hereby amended to read as follows: 315.3.4 Attic, under-floor, concealed spaces and basements. Attic, under-floor, concealed spaces, and basements used for storage of combustible materials shall be protected on the storage side as required for one (1) hour fire-resistance-rated construction. Openings shall be protected by assemblies that are self-closing and are of noncombustible construction or solid wood core not less than one and three quarter (1.75) inches in thickness. Storage shall not be placed on exposed joists. Exceptions: 1. Areas protected by approved automatic sprinkler systems. 2. Group R-3 and Group U occupancies. (16) Chapter 3, Section 319.10.3, is hereby amended to read as follows: 319.10.3 Fuel gas systems. If required by the authority having jurisdiction, LP-gas containers installed on the vehicle and fuel-gas piping systems shall be inspected annually by an approved inspection agency or a company that is registered with the U.S. Department of Transportation to requalify LP-gas cylinders, to ensure that system components are free from damage, suitable for the intended service, and not subject to leaking. CNG containers shall be inspected every three (3) years in a qualified service facility. CNG containers shall not be used past their expiration date as listed on the manufacturer's container label. Upon satisfactory inspection, the approved inspection agency shall affix a tag on the fuel gas system or within the vehicle indicating the name of the inspection agency and the date of satisfactory inspection. (17) Chapter 5 is adopted as written in the International Fire Code with the exception of Section 506.1, which is hereby amended to add the following: 506.1.3 Where required. Key boxes shall be installed to provide access to all buildings with fire sprinkler systems, fire alarm systems and/or elevators. (18) Chapter 9, Section 901.1, is hereby amended to read as follows: 901.1 Scope. The provisions of this chapter shall specify where fire protection and life safety systems are required and shall apply to the design, installation, inspection, operation, testing, and maintenance of all fire protection systems. Such design, installation, inspection, operation, testing, and maintenance shall be performed by qualified personnel. The National Institute of Certification in Engineering Technologies (NICET) is the standard of certification for third party contractors used by the Lewiston Fire Department to determine an individual's qualifications for fire alarm and/or fire sprinkler work. Individuals designing fire alarm or fire sprinkler systems shall be certified NICET Level III or equivalent. Individuals performing inspection, testing, and maintenance on fire alarm or fire sprinkler systems as third party contractors shall be certified NICET Level II or equivalent. Granting of equivalences, and/or revocation thereof, shall be at the exclusive discretion of the fire chief. Individuals shall not undertake work for which they are not competent by way of their education, training, experience, and/or licensure. Individuals with NICET Levels I or II certification shall not work beyond their licensure as outlined by NICET. (19) Chapter 9, Section 901.2, is hereby amended to read as follows: 901.2 Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation, or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. An individual who designs fire alarm or fire sprinkler systems shall hold the appropriate NICET certification or equivalent, as approved by the fire chief, as required by section 901.1 of the International Fire Code, as amended in this chapter. (20) Chapter 9, Section 901.6.3, is hereby amended to read as follows: 901.6.3 Records. Records of all system inspections, tests and maintenance required by the referenced standards and this code shall be maintained. Fixed-fire protection systems inspection, testing and maintenance records noted throughout the International Fire Code and referenced standards shall be submitted to the Lewiston Fire Department in the manner and frequency determined by the fire code official. All documentation submitted to the Lewiston Fire Department shall be true and accurate. Fire protection system inspection, testing, and maintenance companies shall submit fire protection system reports to the Lewiston Fire Department, through the approved website, within fourteen (14) calendar days of the inspection, testing, and/or maintenance. Rejected reports shall be resubmitted to the Lewiston Fire Department, through the approved website, within seven (7) calendar days of the rejection. Deficiencies shall be corrected within thirty (30) calendar days of the report being accepted by the Lewiston Fire Department, unless otherwise required. After deficiencies are corrected, the inspection, testing, and maintenance company shall update the report, through the approved website, within seven (7) calendar days of correcting such deficiency(ies). If another contractor is needed to correct a deficiency (i.e., not the contractor who identified the deficiency), then it shall be the responsibility of the property owner to notify the Lewiston Fire Department that the deficiency(ies) was corrected within seven (7) calendar days of correction of such deficiency(ies). Submitting a report, resubmitting a report, and updating the deficiency status shall be the responsibility of the fire protection inspection, testing, and maintenance companies. Arranging for the inspection, testing, and maintenance required by the International Fire Code and then ensuring deficiencies are corrected within the required timeframe shall be the property owner's, or designated representative's, responsibility. (21) Chapter 9, Section 901.7, is hereby amended to read as follows: 901.7 Systems out of service. Where a fire protection system is out of service, the fire department and the fire code official shall be notified immediately and, where required by the fire code official, the building shall be either evacuated or an approved fire watch shall be provided for all occupants left unprotected by the shutdown until the fire protection system has been returned to service. Where utilized, fire watches shall be provided with not less than one (1) approved means for notification of the fire department and their only duty shall be to perform constant patrols of the protected premises and keep watch for fires. A fire watch may be required twenty-four hours per day for seven days per week (24/7) at the fire chief's discretion. (22) Chapter 9, Section 903.1.2, is hereby amended to add the following: 903.1.2 Residential systems. Unless specifically allowed by this code or the International Building Code, residential sprinkler systems installed in accordance with NFPA 13D or NFPA 13R shall not be recognized for the purposes of exceptions or reductions permitted by other requirements of this code. (23) Chapter 9, Section 903.2, is hereby amended to read as follows: 903.2 Where required. Approved automatic sprinkler systems in new buildings and structures shall be provided in the locations described in Sections 903.2.1 through 903.2.12. An approved automatic fire extinguishing system (NFPA 13 system) shall be installed in all new construction, or change of occupancy, where the fire-flow calculation area as defined in Appendix B, and type of construction requires a fire flow of three thousand (3,000) gallons per minute or more and in the occupancies and locations as set forth in section 903. Exceptions: 1. Unless otherwise required, installation of an automatic fire-extinguishing system in the existing portion of a structure shall not be required, where the addition to the structure is separated by two-hour fire wall with protected openings, and the addition is protected by a monitored automatic fire-extinguishing system. Protection of openings shall be initiated by heat and smoke. 2. Spaces or areas in telecommunications buildings used exclusively for telecommunications equipment, associated electrical power distribution equipment, batteries and standby engines, provided that those spaces or areas are equipped throughout with an automatic smoke detection system in accordance with Section 907.2 and are separated from the remainder of the building by not less than 1-hour fire barriers constructed in accordance with Section 707 of the International Building Code or not less than 2-hour horizontal assemblies constructed in accordance with Section 711 of the International Building Code, or both. (24) Chapter 9, Section 903.4.3, is hereby amended to read as follows: 903.4.3 Floor control valves. Where an NFPA 13 fire sprinkler system is required, an approved supervised indicating control valve, flow switch and drain shall be provided at the point of connection to the riser on each floor in multi-story buildings, either in the riser room, in an interior stairwell, or as otherwise required by the fire code official. (25) Chapter 9, Sections 904.1.1 and 906.2.1, are hereby adopted as written in the International Fire Code. (26) Chapter 9, Section 907.1, is hereby amended to read as follows: 907.1 General. This section covers the application, installation, performance and maintenance of fire alarm systems and their components in new and existing buildings and structures. The requirements of Section 907.2 are applicable to new buildings and structures. The requirements of Section 907.9 are applicable to existing buildings and structures. Notification Devices. When fire alarm systems not required by the International Fire Code are installed, the notification devices shall meet the minimum design and installation requirements for systems that are required by this code. Intent: Non-required fire alarm systems shall provide the same level of occupant notification that required systems provide. (27) Chapter 9, Section 907.2.1, Exception, is hereby deleted and repealed in its entirety. (28) Chapter 9, Section 907.5.2.3, Exception 1, is hereby amended to read as follows: 1. Visible alarm notification appliances are not required in alterations, except where an existing fire alarm system and/or panel is upgraded or replaced, or an entirely new fire alarm system is installed in a building. (29) Chapter 9, Section 907.6.1, is hereby amended to add the following exception: 907.6.1 Wiring. Wiring shall comply with the requirements of NFPA 70 and NFPA 72. Wireless protection systems utilizing radio-frequency transmitting devices shall comply with the special requirements for supervision of low-power wireless systems in NFPA 72. Exception: Installation may be done by a licensed electrician under the guidance of an approved fire alarm contractor. (30) Chapter 9, Section 907.7, is hereby amended to read as follows: 907.7 Acceptance tests and completion. All programming shall be performed by a NICET Level II fire alarm technician. Upon completion of the installation, the fire alarm system and all fire alarm components shall be tested in accordance with NFPA 72 by a NICET Level II fire alarm technician. (31) Chapter 9, Section 907.7.2, is hereby amended to read as follows: 907.7.2 Record of completion. A record of completion in accordance with NFPA 72 verifying that the system has been installed and tested in accordance with the approved plans and specifications shall be completed and provided to the Lewiston Fire Department by a NICET Level II fire alarm technician. (32) Chapter 9, Section 907.8.5, is hereby amended to read as follows: 907.8.5 Inspection, testing, and maintenance. The building owner shall be responsible to maintain the fire and life safety systems in an operable condition at all times. Service personnel shall meet the qualification requirements of NFPA 72 and section 901.1 of the International Fire Code, as amended in this chapter, for inspection, testing, and maintenance of such systems. Records of inspection, testing, and maintenance shall be maintained as required by section 901.6.2 of the International Fire Code, as amended in this chapter. (33) Chapter 9, Section 912.2.3, is hereby amended to add the following: 912.2.3 Separate FDC. Every building provided with a fire sprinkler system, standpipe, standpipe system, or other system providing water for fire extinguishment shall be equipped with a fire department connection. Each building shall be provided with a separate fire department connection. (34) Chapter 11, Section 1101.1, is hereby amended to read as follows: 1101.1 Scope. The provisions of this chapter shall apply to existing buildings constructed prior to the adoption of this code, only, if in the opinion of the fire code official, they constitute a distinct hazard to life and property. (35) Chapter 56 is adopted as written in the International Fire Code. (36) Chapter 57, Section 5704.2.13.1.3, is hereby amended to read as follows: 5704.2.13.1.3 Out of service for one year. Underground tanks that have been out of service for a period of one (1) year shall be removed from the ground in accordance with Section 5704.2.14 or abandoned in place in accordance with Section 5704.2.13.1.4. Upon approval of the fire chief, underground tanks that comply with the performance standards for new or upgraded underground tanks set forth in Title 40, Section 280.20 or 280.21 of the Code of Federal Regulations may remain out of service indefinitely so long as they remain in compliance with the operation, maintenance and release detection requirements of the federal rule. (37) Chapter 80 is adopted as written in the International Fire Code, as amended by Section 102.7 in this adoption. (38) Appendix B, Section B105.1, is hereby amended to read as follows: B105.1 One- and two-family dwellings, Group R-3 and R-4 buildings and townhouses. The minimum fire-flow and flow duration requirement for one (1) and two (2) family dwellings, Group R-3 and R-4 buildings and townhouses having a fire-flow calculation area which does not exceed three thousand six hundred (3,600) square feet (344.5 m 2 ) shall be five hundred (500) gallons per minute for two (2) hours. Fire-flows and flow durations for dwellings having a fire-flow calculation area in excess of three thousand six hundred (3,600) square feet (344.5 m 2 ) shall not be less than one thousand (1,000) gallons per minute for two (2) hours. (39) Appendix B, Section B105.2, is hereby amended to read as follows: B105.2 Buildings other than one- and two-family dwellings, Group R-3 and R-4 buildings and townhouses. The minimum fire flow and flow duration for buildings other than one (1) and two (2) family dwellings, Group R-3 and R-4 buildings and townhouses shall be as specified in Table B105.1(2). Exception: A reduction in required fire flow of up to seventy-five (75%) percent, as approved by the fire chief, is allowed when the building is provided with an approved automatic sprinkler system installed in accordance with Section 903.3.1.1 or 903.3.1.2. The resulting fire-flow shall not be less than one thousand (1,000) gallons per minute for the prescribed duration as specified in Table B105.1(2). A twenty-five (25%) percent reduction in required fire flow is allowed when the building is provided with an approved monitored automatic fire alarm system. The resulting fire flow shall not be less than one thousand (1,000) gallons per minute for the prescribed duration as specified in Table B105.1(2). This reduction shall not be used to eliminate an automatic fire extinguishing system as required by Section 903.2 of this adoption. When an automatic fire extinguishing system is required by Section 903.2 of this adoption, the twenty-five (25%) percent reduction allowed by this exception shall not apply to eliminate the requirement for that system. (40) Appendix B, Table B105.1(1) and Table B105.2, are hereby deleted in their entirety. (41) Appendix C, Section C103.2, is hereby amended to read as follows: C103.2 Average spacing. The average spacing between fire hydrants shall be in accordance with Table C102.1. Exceptions: 1. The average spacing shall be permitted to be increased by ten percent (10%) where existing fire hydrants provide all or a portion of the required number of fire hydrants. 2. The fire chief is authorized to accept a deficiency of up to one hundred sixty (160') feet where existing fire hydrants provide all or a portion of the required fire hydrant service for single family residential units and structures housing no more than two residential units (duplex). Regardless of the average spacing, fire hydrants shall be located such that all points on streets and access roads adjacent to a building are within the distances listed in Table C102.1. Exceptions: 1. The fire chief is authorized to accept a deficiency of up to one hundred (100') feet where existing fire hydrants provide all or a portion of the required fire hydrant service for single family residential units and structures housing no more than two (2) residential units (duplex). 2. The fire chief is authorized to accept a deficiency of up to ten (10%) percent where existing fire hydrants provide all or a portion of the required fire hydrant service for occupancies other than A, E, I and H. 3. The fire chief is authorized to accept a deficiency of up to one hundred (100') feet where existing fire hydrants provide all or a portion of the required fire hydrant service for all occupancies other than A, E, I and H where the property is located on a street corner with public street or road frontage on two (2) sides of the property. (42) Appendix D, Section D101.1, is hereby adopted as written in the International Fire Code. (43) Appendix D, Section D101.2, is hereby amended to add the following: D101.2 Dead-end fire apparatus access road turnaround. Figure D103.1 is replaced with Lewiston Fire Department document titled Fire Apparatus Access Roads. (44) Appendix D, Section D102.1, is hereby amended to read as follows: D102.1 Access and loading. Facilities, buildings or portions of buildings hereafter constructed shall be accessible to fire department apparatus by way of an approved fire apparatus access road designed and maintained to support the imposed loads of the responding fire apparatus and shall be surfaced so as to provide all-weather driving capabilities and in accordance with Lewiston Fire Department document titled Fire Apparatus Access Roads. (45) Appendix D, Section D103.2, is hereby amended to read as follows: D103.2 Grade. Fire apparatus access roads shall not exceed eleven (11%) percent in grade. Exception: Grades steeper than eleven (11%) percent as approved by the fire chief.

(Ord. No. 4555, § 3, 1-10-11; Ord. No. 4601, § 2, 10-28-13; Ord. No. 4712, § 3, 11-27-17; Ord. No. 4770, § 1, 4-13-20; Ord. No. 4784, § 2, 10-26-20)

Ask a question about Lewiston law

Corpus searches the Lewiston sections it holds and shows the ones that match, with their citations. Free, no sign-in.