§ 15-24-800 — Dip tank covers
Municipal Code of Chicago (2026 S-74, current through Council Journal of June 17, 2026) · Municipal Code of Chicago § 15-24-800
Corpus is an independent public-information project, not the official City of Chicago website. Stable reference: corpuslaw.us/code/1266cd72-186b-4a34-9de8-8b45e826f10a
15-24-800 Dip tank covers.
Dip tank covers shall comply with the following: (a) Covers shall be arranged to close automatically in the event of a fire. Such tank covers shall also be arranged for manual operation. (b) Covers shall be constructed of substantial noncombustible materials or if of the tin-clad type, the enclosing metal shall be with locked joints. (c) Chains or wire rope shall be used for cover support or operating mechanism. (d) Covers shall be kept closed when dip tanks are not in use. (Prior code § 129.1-71)
Ask a question about Chicago law