§ 15-24-810 — Hardening and tempering tanks

Municipal Code of Chicago (2026 S-74, current through Council Journal of June 17, 2026) · Municipal Code of Chicago § 15-24-810

Corpus is an independent public-information project, not the official City of Chicago website. Stable reference: corpuslaw.us/code/61c48e53-cb08-4de2-97b2-cc8314488378

15-24-810 Hardening and tempering tanks.

Hardening and tempering tanks shall comply with the requirements of Sections 15-24-760 to 15-24-800 and with the specific requirements of the following provisions: (a) Such tanks shall not be located on or within 20 feet of combustible floors. Such tanks shall not be closer than 20 feet for a furnace or other open-flame heating device, torch or other heat-producing device. (b) Such tanks shall be provided with a noncombustible hood and vent, and shall be vented directly to the outside of the building and shall otherwise comply with the requirements of Title 14M. Such vents and hood shall not be closer than 18 inches to any combustible materials. (c) Each such tank shall be equipped with a high temperature limit switch so arranged to sound a suitable audible alarm when the temperature of the quenching medium reaches 50 degrees below the flashpoint. (d) Such tanks having a capacity of over 500 gallons or having a liquid surface area of 25 square feet or more shall be protected as specified in Section 15-24-790(b) or (c) of this Code. (e) Air under pressure shall not be used to fill or to agitate the quenching medium in the tanks. (Prior code § 129.1-72; Amend Coun. J. 10-7-20, p. 21791, Art. VI, § 44)

Ask a question about Chicago law

Corpus searches the Chicago sections it holds and shows the ones that match, with their citations. Free, no sign-in.