§ 18-28-1107.7.1 — Liquid receivers
Municipal Code of Chicago (2026 S-74, current through Council Journal of June 17, 2026) · Municipal Code of Chicago § 18-28-1107.7.1
Corpus is an independent public-information project, not the official City of Chicago website. Stable reference: corpuslaw.us/code/43d50b74-b4d0-44da-85e6-ee3093465ad5
18-28-1107.7.1 Liquid receivers.
All systems containing 100 pounds (45 kg) or more of a refrigerant, other than systems utilizing non-positive displacement compressors, shall have stop valves, in addition to those required by Section 18-28-1107.7, on each inlet of a receiver. Stop valves shall not be required on the inlet of a receiver in a condensing unit, nor on the inlet of a receiver which is an integral part of the condenser.