§ 18-28-1106.9 — Flammable refrigerants
Municipal Code of Chicago (2026 S-74, current through Council Journal of June 17, 2026) · Municipal Code of Chicago § 18-28-1106.9
Corpus is an independent public-information project, not the official City of Chicago website. Stable reference: corpuslaw.us/code/32e99174-1d8c-4088-8d6f-9664c60f8c66
18-28-1106.9 Flammable refrigerants.
Where refrigerants of Groups A2, A3, B2 and B3 are used, the machinery room shall conform to the Class I, Division 2, hazardous location classification requirements of NFPA 70. Exception: Ammonia machinery rooms.
Ask a question about Chicago law
Corpus searches the Chicago sections it holds and shows the ones that match, with their citations. Free, no sign-in.
